Service Menu - Helios ECgreen Vent KWL EC 800 S Pro WW Notice D'installation Et D'utilisation

Masquer les pouces Voir aussi pour ECgreen Vent KWL EC 800 S Pro WW:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
Time and date
Time & date

Service menu

Enter code 1616 to access the service menu.
49 -
50 -
04 -
Select desired menu by scrolling.
Menu 01 – Mode
49 -
50 -
25 -
04 -
03 - Filter timer
Central Ventilation Units KWL EC.. S Pro/WW
Andere Einstellungen
Zurück auf Werkseins
Access the
Modus
selected
Hw-Einstellung
menu
Ventilatorenkalibrier
Andere Einstellungen
User lock
Zurück auf Werkseins
Factory reset
Modus
Hw-Einstellung
Ventilatorenkalibrier
Manual
ventilation
mode
DCV: The unit ventilates according to the requirements of the air quality sen-
sor, e.g. CO
, RH (0-10 V control signal).
2
CAV: The unit ventilates according to the selected flow rate and the required
temperature.
VAV: The unit runs at constant pressure and variable flow rate.
Menu 02 – Hw setting (Hardware)
50 -
01 -
04 -
05 -
Operating
signal, logic of
potential-free
contact
– Operating signal potential-free contact (7-8):
The logic of the connected potential-free contact can be set as follows: as
N. closed (normally closed) or N. open (normally open).
– Hot water heater battery frost protection:
Behaviour of extract air fan for hot water heater battery frost protection
Selection: Extract air fan on/off when hot water heater battery frost pro-
tection triggered.
16
Zurück auf Werkseins
Modus
Hw-Einstellung
Ventilatorenkalibrier
Filterkalibrierung
Fan calibration
Fan calibration
Hw setting
Digital Output RUN (7-8)
N.closed
Water antifreeze outlet fan
Water Frost prot. output
Stop
Stop
Ventilation
according to
the require-
ments of the
air quality
sensor
Behaviour
of extract air
fan with hot
water heater
battery frost
protection