Setup And Commissioning - STEINEL IS 3180-24 Consignes D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

12

Setup and Commissioning

IS 3180-24
IS 3360-24
IS 345-24
Test mode
• Ensure that the sensor is in test
mode.
- set time delay to minimum
setting of 5 seconds
- set light level to maximum
("day" setting, light level
function overridden - factory
setting)
• Turn power ON at the circuit
breaker (lights will turn ON).
After a warm up period of up to
one minute, lights will turn OFF
if the sensor does not detect
motion.
www.steinel.net
(800) 852-4343
• Walk in view of sensor, lights
should turn ON. Be still for 5
seconds and lights will turn
OFF.
Important: Only select time and
light level setting with the lens in
place.
Light level
The light level feature allows
lighting to remain OFF
during daylight, regardless of
occupancy. Daytime operation
is at 200 footcandles (factory
setting). Nighttime operation is at
.2 footcandles.
Setup and Commissioning
IS 3180-24
IS 3360-24
IS 345-24
Light level teach mode
The light level teach mode reads
the ambient light level in the
space and selects this amount for
the light level setting.
• Turn the light level setting to
• After 10 seconds, the value
of the ambient brightness is
saved.
• This value is also available
after a power failure if the
potentiometer is set to teach
mode at power up.
Time delay
Time delay is the period of time
lights remain on after the last
detection. Adjustment ranges
from 5 seconds to 15 minutes.
Factory setting is 5 seconds.
Pulse function
For use with a time delay relay,
the pulse function activates the
output for 2 seconds.
After setup and commissioning
tests are complete, adjust
the time delay and light level
settings to fit the application
needs.
5 sec.-15 min.
www.steinel.net
(800) 852-4343
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Is 3360-24Is 345-24

Table des Matières