BBPR models (GS6)
Actuators with battery backup position recovery system (on-off wiring mandatory)
BBPR models integrate a battery pack monitored by an electronic board inside the actuator. Its function is to re-
lay in case of power supply failure on terminal PIN 1,2 and 3 of the actuator. The BBPR system can be set on
different position like normally open (NO) or normally closed (NC). It depends on the application.
The electronic board monitors the battery pack and check the status of battery (cycle load and failure)
If a battery failure is detected , a contact on PIN 65 and 66 switch off. It's possible to use this contact to be
aware that there is a failure on battery in the actuator without remove cover and plan the replacement.
BBPR option requires ON/OFF mode.
Loading electronic board
LED
DESCRIPTION
D19
L1
Actuator operating into opening
green
D18
L2
Actuator operating into closing
red
Battery status :
ACT
 S low blinking (1s) : battery charged.
L3
green
 R apid blinking (0.5s) : battery charging
Error detected:
 T imestamp memory empty/scheduler selected
ERROR
 C lock failure
L4
red
 E xcessive temperature
 E xcessive torque
HORO
L5
Orange Weekly scheduler functioning mode
MANU
L6
Orange manual / Bluetooth
WIRE
L7
Orange Electric wiring mode
CONNECTEUR
C1
17 (-) · 18 (+)
C2
F (+) · F (-) · T (+) Battery unit connector
C3
A · B · C
C4
1)
D3 · D4
C5
1)
65 · 66
C6
A · 0 · B
J1
Bluetooth
®
activation jumper
1) The auxiliary cables must be connected to inside installation only
The factory default configuration is "normally closed"
Following a power failure, the BBPR unit will reset after 4 minutes
DSBA3801 • Rév. 02/06/2021
®
functioning mode
DESCRIPTION
power supply connector
Motor connector
Failure feedback connector
Dry contact
Charging feedback connector
Dry contact
RS485 connector
L4
J1
L3
C3
C2
C1
Battery voltage
Battery capacity
Charging current
initial battery charge duration
Charging status feedback relay
Failure feedback relay (D3/D4)
Temperature
L6
C6
L5
L7
L1
C4
L2
C5
24 V DC
600 mAh
180 mA
3,5 h
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C