Io-Link Interface (Xf1/ ); Io-Link Interface (Xf1/ 5.2.3 Auxiliary Voltage Connection (Xd1); I/O-Port (X00 - Balluff BNI IOL-314-S52-P012 Notice D'utilisation

Masquer les pouces Voir aussi pour BNI IOL-314-S52-P012:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

BNI IOL-314-S52-P012 / BNI IOL-314-S52-P071
Network interface – Digital hub
5
Installation and connection (continued)
5.2.2
IO-Link interface (XF1/
1
2
4
BNIXXXX
3
Fig. 5-1:
Top view of M12 plug, A-coded
Pin
BNI IOL-...-P012
00
1
Supply voltage for the
module and connected
sensors (U
)
S1
2
Supply voltage for
00
actuators (U
)
A
3
GND, reference potential
4
C/Q, IO-Link data transmission channel
Tab. 5-1:
Pin assignment of IO-Link interface
00
5.2.3
Auxiliary voltage connection (XD1)
The BNI IOL-314-S52-P071 variant has an L-coded M12
auxiliary voltage connection. This connection allows more
00
power to be supplied for the sensor and actuator systems.
Fig. 5-2:
Top view of M12 plug, L-coded
Pin
Signal
1
Power supply U
S2
2
GND, reference potential U
3
GND, reference potential U
4
Actuator supply U
A
5
Function ground
Tab. 5-2:
Pin assignment of auxiliary voltage connection (XD1)
www.balluff.com
)
Signal
BNI IOL-...-P071
01
00
01
Supply voltage for the
module (U
)
S1
01
00
01
01
00
01
01
00
0 1
A
S2
5.2.4
I/O-Port (X00...X07)
Port X07 can be configured as a standard I/O port
or as an extension port.
Standard I/O-Port (X00...X07)
2
5
1
3
4
Fig. 5-3:
Top view of M12 socket, A-coded
Pin
Signal
1
+24 V, sensor supply
2
Digital input/output
3
GND, sensor supply, inputs, outputs
4
Digital input/output
5
Function ground
Tab. 5-3:
Pin assignment of standard I/O port (X00...X07)
For the digital sensor inputs, see guideline
via inputs EN 61131-2, type 1 and type 3.
Extension port (X07)
2
5
1
3
4
Fig. 5-4:
Top view of M12 socket, A-coded
Pin
Signal
1
+24 V, sensor/module supply
2
+24 V, actuator supply
3
GND, sensor/actuator supply
4
C/Q communication line
5
Function ground
Tab. 5-4:
Pin assignment of extension port (X07)
english
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bni iol-314-s52-p071

Table des Matières