icon will appear in the standard screen. You can then press the rotary knob/pushbutton to
switch between control of group 1 and group 2. If 2 follows 1 is selected, both groups are assigned
their own strategy, but group 2 will follow the program for group 1.

5.5 Setting the control strategy

The controller lets you use the room control and/or weather-compensated control strategies in
various ways. You can select a control strategy via Menu > Settings > System > Control settings.
When implementing these changes, the user level must be set to Extended mode
i
(See paragraph 5.1).
Specific settings for weather-compensated control
If you have opted for a weather-compensated control strategy, a number of extra settings are
available via Menu > Settings > System > OTC settings.
Heating curve:
- Base outside: outside temperature base point
- Base flowtemp: flow temperature base point
- Climate outside: outside temperature climate point
- Climate flowtemp: flow temperature climate point
- Curvature: degree of curvature of the heating curve, depending on your central heating
system. Select the relevant type of heaters: underfloor heating, radiators or convectors.
This will provide more comfort early and late in the year.
EN