Connecting the mains voltage
Hazard warning
WARNING!
NOTE!
CALEC
ST II
®
Danger of electrocution!
Touching or gripping live electrical parts can cause an electric
shock, which may result in burns, paralysis or death.
• The device should only be opened, installed or repaired when
the power has been switched off.
• Only specialist technicians are authorised to work on or with
mains voltage.
They must comply with the applicable regulations.
• Only the screw-type terminals in the separated area on the
left in the terminal compartment should be used to connect
the device to the mains supply.
Calibrated device!
• The device must be protected by an external overcurrent
protective device (max. 10A) so that the unit shuts down sa-
fely in the event of an electrical fault.
The power supply must be designed to ensure that it has
adequate protection against intentional interruption and that
it can be shut down for maintenance.
• A marked 2-pole isolating device is mandatory. Alternatively,
a 2-pole isolating overcurrent protective device can be used.
However, it must not be possible to the circuit for the totaliser
to be disconnected independently of the heating or cooling
system.
• The connection cable must have a temperature resistance
> 65°C.
65