Commissioning; Completing Installation; Appliance Handover; Recommissioning - Stiebel Eltron SHZ 30 LCD Utilisation Et Installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION

Commissioning

Note
You can only change the output and operating mode
when the power supply is isolated.
E Single circuit operation
Z Dual circuit operation
B Manual rapid heat-up operation
1 Output 1
2 Output 2
3 Output 3
Note
For special circuits without external contactors for tariff
changeover (dual circuit operation, dual meter measur-
ing, 1/N/PE ~ 230 V), please see chapter "Specification /
Wiring diagrams and connections".
f Select the output and operating mode with the switches on
the control unit electronic assembly and select the required
connection (see chapter "Specification / Wiring diagrams and
connections").
f Tick the selected connected load and voltage on the type
plate with a ballpoint pen.
f If required, connect a remote control for rapid heating to the
mains terminal.

10.4 Completing installation

f Plug the 5-pole plug-in connection of the connecting cable
onto the electronic assembly for operation, position X2.
f Position the bottom cap.
f Insert the 4 screws.
Sealed unvented (pressure-tested) operation:
f Connect the safety assembly with the appliance by securing
the pipes to the appliance with screws.
Open vented (non-pressurised) operation
f Connect the appliance to the tap.
11. Commissioning
11.1 Commissioning
f Open the DHW valve until the appliance has filled up and the
pipes are free of air.
f Observe the maximum permissible flow rate with a fully
opened tap (see chapter "Specification / Data table").
f Sealed unvented (pressure-tested) operation:
If necessary reduce the flow rate at the butterfly valve of the
safety assembly.
Fit the discharge pipe of the safety assembly with a constant
slope.
Observe the information in the installation instructions of the
safety assembly.
34
| SHZ LCD
f Switch the mains power ON.
f Check the function of the appliance. If necessary, check the
function of the rapid heater.
f Sealed unvented (pressure-tested) operation:
Check the function of the safety assembly.
If an outlet temperature of 55 °C is achieved after commission-
ing, the temperature is automatically balanced and scale build-up
detection is switched on. This interrupts heat-up for approx. 5
minutes.

11.1.1 Appliance handover

f Explain the appliance function to users and familiarise them
with its operation.
f Make users aware of potential dangers, especially the risk of
scalding.
f Hand over these instructions.

11.2 Recommissioning

See chapter "Commissioning".

12. Settings

(See also chapter "Specification / Wiring diagrams and connec-
tions").

12.1 Switching on commercial mode

f To switch on commercial mode, replug the relevant jumper.
S Jumper ECO (energy saving mode)
E ECO on (factory setting)
A ECO off (commercial mode)

12.2 Switching on reverse control

f To switch on reverse control, replug the jumper.
R Reverse control jumper
E Reverse control on
A Reverse control off (factory setting)

13. Shutting down

f Disconnect the appliance from the mains at the MCB/fuse in
the fuse box.
f Drain the appliance. See chapter "Maintenance / Draining the
appliance".
www.stiebel-eltron.com