Examples of Circuit Diagrams
Automatic Motor Restart.
Can cause death, serious personal injury or property damage.
Do not use automatic reset mode when unexpected automatic restart of the motor can occur and cause injury to persons or damage
to equipment.
The Start command (e.g. via the PLC) must be canceled before a Reset command is given, since an automatic restart is executed after
the Reset command when the Start command is still pending. This applies in particular in the case of motor protection tripping. For
safety reasons, it is recommended to integrate the group fault output (terminals 95 and 96) into the controller.
Main circuit, option 1:
Standard switching with optional main contactor
1)
L1
3/N/PE 400 V AC , 50 Hz
L2
L3
Q1
(optional
semiconductor
F3
fuse)
K1
L1
L3
L2
G1
T1
T2
T3
U1
V1
W1
M1
M
3~
PE
Rotation reversal in
Main circuit, option 2:
inside delta circuit
Inside delta circuit
1)
L1 3/N/PE 400 V AC , 50 Hz
L1 3/N/PE 400 V AC , 50 Hz
L2
L2
L3
L3
Q1
Q1
K1
F3
L1
L2
L3
G1
G1
T1
T2
T3
V1 W1
U1
M
3~
M1
M1
W2
V2
U2
PE
PE
F3 = optional semiconductor fuse
1)
Permitted values for main and control voltage, see technical data.
3ZX1012-0RW44-1AA1
Control circuit, option 1:
Activation of an optional main contactor
as well as activation via PLC
L1 1/N/PE 230 V AC , 50 Hz
F2
A1
L+
G1
Switch-on duration
PE
A2
13
PE
N
Control circuit, option 2
Activation via PLC
L1 1/N/PE 230 V AC , 50 Hz
1)
F2
L1
L2
L3
A1
G1
T1
T2
T3
PE
A2
V1
U1
W1
M
3~
W2
V2
U2
PE
N
WARNING
1)
+24 V DC
PLC outputs
M
Start
Reset
L-
IN1
IN2
IN3
14
23
24
33
34
95
No action
No action
Group action
K1
1)
+24 V DC
PLC outputs
M
Start
L+
L-
IN1
IN2
13
14
23
24
33
Switch-on
No action
No action
duration
PLC inputs
PTC type A /
Thermoclick
IN4
T1
T2
+
96
98
NSB0_01496
PLC inputs
Reset
PTC type A
Thermoclick
IN3
IN4
T1
T2
+
34
95
98
96
NSB0_01498
Group fault
17