Analog Setpoint - Outlet Pressure - ASCO Numatics Sentronic Plus 614 Série Manuel D'installation

Régulateur de pression numérique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION
3.

ANALOG SETPOINT - OUTLET PRESSURE

Setpoint offset
The pressure setpoint zero can be changed via the DaS software. Switch to "Custom" in the "Setpoint setting" section.
The zero range is max. -50 ... +100 %.
Max.
outlet pressure
PMR
+50% PMR
SHUT-OFF
50 mV
0
0.1 mA
0
4.08 mA
4
-50% PMR
Offset adjustment
CAUTION: Outlet pressures above the maximum outlet pressure (PMR) are not controlled by the valve, i.e. the max.
outlet pressure is limited to the PMR.
In order to avoid damaging the sensor, the supply pressure must always be less than the maximum inlet pressure
(MAP) (see Table).
Setpoint span
The pressure span of the setpoint can be changed via the DaS software. Switch to "Custom" in the "Setpoint setting"
section. The span is between +10 and +150 %.
Max. outlet
pressure
PMR
Max. outlet
pressure
PMR
SHUT-OFF
50 mV
0
0.1 mA
0
4.08 mA
4
Span adjustment
The span can be set to max. 100% of the maximum outlet pressure (PMR).
It can only be decreased.
5 V
10 V
10 mA
20 mA
12 mA
20 mA
10 V
20 mA
20 mA
Max.
Max.
outlet pressure
inlet pressure
PMR
MAP
(bar)
(bar)
0 - 100 mbar
2
0 - 500 mbar
2
0 - 1 bar
2
0 - 2 bar
3
0 - 3 bar
8
0 - 5 bar
8
0 - 6 bar
12
12
0 - 10 bar
14
0 - 12 bar
1)
18
0 - 16 bar
1)
22
0 - 20 bar
2
0 - 30 bar
)
40
2)
0 - 50 bar
60
1)
For DN3 and DN6 only.
2)
For DN6, Ms, only.
GB
IM14229-7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sentronic plus 614 série

Table des Matières