Operating Elements; Operating Modes - ASCO Numatics Sentronic Plus 614 Série Manuel D'installation

Régulateur de pression numérique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GB
1.2

OPERATING ELEMENTS

1
2.3
5
2.1
6
7
8
1.3

OPERATING MODES

Shut-off:
If the setpoint falls below 0.5 %, the coil current is switched off and the valve is fully exhausted.
Overtemperature:
If the temperature of the internal control electronics exceeds 100°C, the operating mode is switched to AUTOSAFE.
Undervoltage / overvoltage:
If the supply voltage is less than 18 V or more than 30 V, the coil current is switched off and the valve is fully
exhausted..
Autosafe:
If the coil current exceeds a certain value, dependent on the mechanics, for more than 20 seconds, the output
current is limited to max. 70% to prevent the valve from overheating.
IM14229-4
3
1
Proportional solenoid coil
2.1
Pressure supply
2.2
Pressure outlet
2.3
Exhaust
3
Power supply, M12 connector or
7-pin DIN connector
4
Ground connection M4
5
Mounting hole
6
Serial communication RS232 (PC connection)
7
LC display
8
2 pushbuttons
4
2.2
5
INSTALLATION