ASCO Numatics Sentronic Plus 614 Série Manuel D'installation page 6

Régulateur de pression numérique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GB
View on solder side
of female connector
(Output)
PRESSURE SWITCH OUTPUT
+ 30V max.
NPN
Feedback = Setpoint
or
PNP
Feedback = Setpoint
or
+ 30V max.
NPN
Feedback ≠ Setpoint
or
PNP
Feedback ≠ Setpoint
!
CAUTION - BE SURE TO FOLLOW THESE INSTRUCTIONS!
1) The coil must only be supplied with 24 V DC ±10 % and a max. ripple of 10 % (no supply via
diode bridge). Overvoltage or a ripple rate exceeding 10 % can damage the electronics.
2) The max. current at pin 7 is 500 mA (NPN/PNP output). Pin 7 is protected against short circuit
and overload.
3) If a relay (inductive load) is connected to the pressure switch output, a freewheel diode or a
varistor must be used.
4) Do not solder unused pins on the connector.
5) In case of an interruption in the pressure supply, shut off the power supply (+24V) or switch
the set point to zero to avoid excessive heating of the coil.
6) Grounding for personal protection must be done at the PE terminal (ØM4) on the body (see
diagramme opposite).
7) Use a shielded cable for EMC protection. Connect the shield to ground and to the connector
body.
IM14229-6
7-pin DIN connector
Supply voltage
+24V
Supply voltage GND
Setpoint
10V
(or 0-20 mA or 4-20 mA)
Setpoint GND
Not used
Outlet pressure feedback
0-10V (or 0-20mA or 4-20mA)
NPN if setpoint
is reached
I = 500 mA max.
PNP if setpoint
0V
is reached
I = 500 mA max.
NPN if setpoint
is not reached
I = 500 mA max.
PNP if setpoint
is not reached
I = 500 mA max.
INSTALLATION
Connector on
electronic card
NPN
PNP
NPN
PNP
PE
ØM4
2