don off the working area and check that the lifting gear is in
perfect condition.
Never work alone. Always wear a hard hat, safety glasses
and safety shoes and, if necessary, a suitable safety belt.
Before carrying out welding works or using electrical de-
vices, check to ensure there is no danger of explosion.
People working in wastewater systems must be vaccinated
against the pathogens that may be found there. For the
sake of your health, be sure to pay meticulous attention to
cleanliness wherever you are working.
Make sure that there are no toxic gases in the working area.
Observe the health and safety at work regulations and make
sure that a first-aid kit is to hand.
In some cases, the pump and the pumping medium may be
hot and could cause burns.
For installations in areas subject to explosion hazards, spe-
cial regulations apply!

TECHNICAL DATA

Operating voltage
• 1/N/PE x 230 V, 50 Hz (AD 00 E)
• 3/N/PE x 230/400 V, 50 Hz
Power consumption
• max. 2 W (Standby <1W)
Switching capacity
• AD 00E 1 x 2.2 kW AC3, 230 V
• AD... 1 x 4 kW AC3, 400V
• AD 910 1 x 5,5 kW AC3, 400V
Control voltage 230 VAC / 12 VDC
Ambient temperature
• -20° Celsius to 50° Celsius
Humidity Up to 90rH with no condensation
Terminals up to 2.5 mm²
Housing dimensions
• H 275 x W 250 x D 155
Housing protection class IP 44
Weight approx. 2 kg
Motor protection
• AD 00: ohne
• AD 25: 2,5-4,0 A
• AD 46: 4,0-6,0 A
• AD 610: 6,3-9,0 A
• AD 910: 9,0-12 A
Pre-fuse
• AD 00-610: 16 A
• AD 910: 20 A
DESCRIPTION
Electronic control unit for level control of one d.o.l. starting
submersible pump.
Up to three level contact sensors can be connected.
The control unit incorporates mains-dependent LED fai-
lure indicators and an alarm buzzer to indicate faults. One
potential-free centralised alarm contacts can be used as
additional remote failure indicator. An optional 9V rechar-
geable battery can also be fitted to sustain an alarm facility
even if a power cut occurs. The battery pack can supply the
alarm system with power for about one hour of continuous
use.
EMC
Our standard submersible pumps and accessories when
installed as specified and used as intended meet the pro-
tective requirements of the EMC Directive 2014/30/EU,
and is suitable for use in domestic and commercial areas
of the public power supply network. When connected to an
industrial mains supply in an industrial plant with the power
supply provided by a company-owned high-voltage trans-
former, it is to be expected that there will be insufficient
immunity to interference.
OPERATION
NOTICE! Operate the control in dry rooms only and keep the
housing closed at all times.

Automatic operation

Automatic operation is the normal operating mode of the
unit. The Manual-0-Automatic selector switch for the pump
must be set to the "Automatik" position for this operating
mode. The pump is switched on and off again automatically
depending on the wastewater level in the collecting cham-
ber. The green "Betrieb Pumpe" (Pump operation) indicator
lights up when the pump is operating.
Manual operation
In case of a malfunction in automatic operation, the collec-
ting chamber can be drained manually as well. For this ac-
tion, set the selector switch to the "Hand" (Manual) position.
The pump will now operate continuously and independently
of the wastewater level.
NOTICE! If the "Hand" (Manual) setting is actuated for too long
at a time, the pump may draw in air. Certain pump types need
to be vented in this case, since they would not pump otherwise.
Shutting down the pump
Set the rocker switch to "0". The pump is shut down.
FAULTS
NOTICE! Repairs and maintenance work on the control unit
or the pump must be carried out by a qualified electrician
only!