E-1: TERMINAL LABEL
A low voltage remote control wiring interface is provided on the unit.
The connections for the low voltage remote wiring are located on
two terminals adjacent to the exhaust fan outlet (or adjacent to the
supply fan outlet on the 7000 unit). All field installed wiring must be
low voltage class II.
R
W
C
EMOTE
ALL
ONTROL
Optional wall control requires a 4 wire LVT-24 gauge (or
equivalent). This remote wall control runs on 12 VDC.
L
V
C
OW
OLTAGE
ONTROLS
All other terminals are dry contacts.
Low Voltage terminal control consists of the following:
W
C
ALL
ONTROL
4 wire LVT 24 gauge minimum
ON-OFF
24 VAC, needs dry contact. For example, can be used for a timer
or motion sensor.
LOW - COMMON - HIGH
Remote fan switching requires a single pole, double throw switch
(SPDT)
F
I
R
O
AN
NTERLOCK
ELAY
UTPUT
Dry contact closes on ventilation or defrost. Used to control
external fan.
WALL CONTROL
COMMANDE MURALE
Black/Noir
Red/Rouge
ON-OFF/
MARCHE-
ARRÊT
F
CLASSE 2 BASSE
F
NOTE:
Use of 24 VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
L'utilisation d'un circuit 24
VCA nécessite des contacts
isolés (ex. thermostat) pour
éviter l'interconnexion des
sorties de Classe 2.
VE0466A
TERMINAL CONTROL DIAGRAMS
(FF)
Green/Vert
Yellow/Jaune
LOW
BASSE
COMMON
COMMUN
HIGH
HAUTE
CLASS 2 LOW
VOLTAGE /
TENSION
Appendix E
E-2: WALL CONTROL CONNECTION
Two types of remote wall controls are available:
1. Slide Switch Wall Control with fan switch and dehumidistat
control (for 6LC, V6LC, 12LC and V12LC units).
2. Pool Plus Wall Control with fan mode selection, dehumidistat
control and high speed recirculation mode (for 7000 unit).
The remote wall controls work with the microprocessor electronic
control within the unit to control ventilation sequences. Each wall
control has different features and require 4-wire connection to the
unit as shown below.
Without the wall control, fans can be operated with a remote fan
switch as shown in Appendix E-4.
NOTE:
When using a wall control, never use the the LOW, COMMON and
HIGH terminals.
COMMANDE MURALE
Black/Noir
Red/Rouge
ON-OFF/
MARCHE-
ARRÊT
F
F
NOTE:
Use of 24 VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
L'utilisation d'un circuit 24
VCA nécessite des contacts
isolés (ex. thermostat) pour
éviter l'interconnexion des
sorties de Classe 2.
21
WALL CONTROL
Green/Vert
Yellow/Jaune
LOW
BASSE
COMMON
COMMUN
HIGH
HAUTE
CLASS 2 LOW
VOLTAGE /
CLASSE 2 BASSE
TENSION
Wall
Control