5. Installing the unit

5.1. Hanging the unit body

s s s s s Bring the indoor unit to an installation site as it is packed.
s s s s s To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
s s s s s When lifting with a lifting machine, in order to protect against damage,
reverse the unit body as is packed with the packing cap and lift it.
[Fig. 5.1.1] (P.2)
A Drain pipe side
B Unit body
C Packing cap
D Lifting machine

6. Refrigerant pipe and drain pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the re-
frigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commer-
cially available insulating material (with a heat-resisting temperature of more than
100 °C and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form
polyethylene's specific gravity of 0.03 and thickness given below) onto all pipes
which pass through rooms.
1 Select the thickness of insulating material by pipe size.
Pipe size
6.4 mm to 25.4 mm
28.6 mm to 38.1 mm
2 If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating
material's thickness more than those given in the table above.
3 If there are customer's specifications, simply follow them.

6.3. Request for refrigerant piping connection

Description of parts to be used
No.
Work procedures
Mount the provided pipe insula-
tion (1) on the liquid pipe of the
refrigerant piping, and then mount
the flare insulation (2) on the gas
pipe.
1
Fixing of insulated pipe
2
Fixing of flare insulation
3
8
Insulating material's thickness
More than 10 mm
More than 15 mm
Detail of work
"INNER" and "OUTER" are marked on the in-
side of the flare insulation. Mount the portion
marked "INNER" near the unit body and the
portion marked "OUTER" on the field piping
side.
• Fasten the insulated pipe with the insula-
tion tape.
• Firmly secure the insulation with the pro-
vided tie band (4) at the position indicated
on the drawing.
• Fasten the flare insulation with the provided
tape (3).
• Fasten with the provided tie band (4) at the
position indicated on the drawing.
5.2. Confirming the unit's position and fix-
ing hanging bolts
s s s s s Use the gage supplied with the panel to confirm that the unit body and
hanging bolts are positioned in place. If they are not positioned in place,
it may result in dew drops due to wind leak. Be sure to check the positional
relationship.
s s s s s Use a level to check that the surface indicated by A A A A A is at level. Ensure
that the hanging bolt nuts are tightened to fix the hanging bolts.
s s s s s To ensure that drain is discharged, be sure to hang the unit at level using
a level.
Caution:
Be sure to install the unit body at level.
[Fig. 5.2.1] (P.2)
B Indoor unit's bottom surface
(Surface to which a decorative panel is attached)
6.1. Refrigerant pipe and drain pipe specifi-
cations
Model
Item
Refrigerant pipe
Liquid pipe
(Flare connection)
Gas pipe
Drain pipe
6.2. Refrigerant pipe , drain pipe and filling
port
[Fig. 6.2.1] (P.3)
A Refrigerant pipe (liquid pipe): HP
C Hanging bolt pitch
E Filling port
Item to be observed
• Using the flare insulation of a different model may
result in condensation forming. Check the model
name on the insulation and be sure to use the cor-
rect one.
• To prevent a gap from forming near the unit's side
plate, be sure that the flare insulation firmly con-
tacts the unit's side plate before mounting.
• Incorrectly mounting the "INNER" and "OUTER"
sides of the insulation may result in condensation
forming.
Seal the slit securely so that there are no openings.
Be sure to mount the insulation so that the slit is on
the top.
Seal the slit securely so that there are no openings.
Be sure to mount the insulation so that the slit is on
the top.
20·25·32·40 50 · 63 · 80
100 · 125
ø6.35
ø9.52
ø12.7
ø15.88
ø19.05
VP-25
B Drain pipe
D Refrigerant pipe (gas pipe): LP
Reference drawing
[Fig. 6.3.1] (P.3)
[Fig. 6.3.2] (P.3)
[Fig. 6.3.2] (P.3)
[Fig. 6.3.3] (P.3)
(Note *3)
[Fig. 6.3.3] (P.3)
(Note *4)