Télécharger Imprimer la page

Lenze L-force Communication INTERBUS E84AYCIB Instructions De Montage page 10

Publicité

X206 IN
Pin
Signal
1
RS485: DO1 not inverted (input)
2
RS485: DI1 not inverted (output)
3
Ground
4
n. c.
5
DC 5 V (output)
6
RS485: DO1 inverted (input)
7
RS485: DI1 inverted (output)
8
DC 5 V (output)
9
n. c.
Cable
Type
3 x 2 (twisted in pairs, with common shielding)
Rigid
> 0.2 mm
< 96 W/km
Specific resistance
Characteristic
l
impedance
l
Effective capacitance
< 60 nF/km (f = 800 Hz)
Example
PHOENIX CONTACT: IBS RBC METER−T, order no. 28 06 28 6
Baud rate
Cable length between the single INTERBUS nodes
500 kbit/s
max. 400 m
2 Mbit/s
max. 150 m
EDK84AYCIB DE/EN/FR/ES/IT 3.0
X205 − X206/X207 − LED
2
120 W ± 20 % (f = 64 kHz)
100 W ± 15 W (f > 1 MHz)
X207 OUT
Pin
Signal
1
RS485: DO2 not inverted (output)
2
RS485: DI2 not inverted (input)
3
Ground
4
5
DC 5 V (output)
6
RS485: DO2 inverted (output)
7
RS485: DI2 inverted (input)
8
DC 5 V (output)
9
RBST (signalling input)
10
3
l

Publicité