These instructions should be kept with the unit.
Mounting
Mounting location
• The SEH62.1 time switch is designed for indoor use
Measures to be taken to avoid radio interference
• Do not install the time switch near strong electromagnetic fields
• Inductive components near the time switch must be fitted with in-
terference suppressors (RC units or varistors)
• Ensure adequate air circulation to dissipate the heat generated
during operation
• In general, standard cable can be used. If the time switch must be
installed in environments with strong electromagnetic fields,
shielded cable should be used
Mounting choices
The time switch can be mounted as follows:
A
On top hat rails.
Type of rail: EN 50 022-35 x 7.5, min. 60 mm long.
B
Wall-mounting with 2 screws.
2 fixing holes are provided.
C
Flush panel-mounting with standard elements, e.g. 1 top hat rail
100 mm long, 2 hexagonal spacers, washers and screws.
D
In protective housing ARG62.22 (when used outside control
panels).
A
B
The connection terminals must be freely accessible.

Electrical installation

Precautionary measures
• Ensure that local safety regulations are complied with
• Between the connection terminals and the mounting plate or metal
covers, there should be a minimum clearance 8 mm
• The connection terminals must be protected by a plastic cover
• Never open the time switch
• Note the maximum switching capacity of the relay contacts: AC 240
V / 6 A (res.), 3 A (ind.)
Internal diagram
Q11
L
D1 M
N
Q12
Q14
L, N
AC 230 V mains supply
M, D1
Digital input (momentary contact closure)
Q...
Digital output
(choice of voltages: AC 24...230 V)
Siemens Building Technologies / HVAC Products
C
D
Commissioning
LCD
Status line
ON OFF AUTO MANUAL
Prg 1 2 3 4 5 6 7 8
Program selection
Su Mo Tu We Th Fr Sa
Weekday
Time/setup title line
Operating elements
The time switch has 3 buttons with the following functions:
Button for confirming a selected or entered value. This
SEL
button also serves as a manual ON/OFF switch for over-
riding the programmed switching sequences
+
Buttons for setting and displaying the time of day, week-
day and switching program
-
Programming
Setting the current time of day, weekday and count-
down timer
What
Press the + and - buttons simultane-
1
Initialization
ously for 5 seconds in normal opera-
tion so that TIME appears flashing
Press the SEL button within 1 min-
12 / 24-hour
ute after initialization, then press the
2
format
+/- buttons to select the display for-
mat. Confirm with the SEL button
After selection of the time format,
Set the cur-
press the +/- buttons within 1 minute
rent time of
3
to set the current time of day. Con-
day
firm with the SEL button
After setting the current time of day,
Set the cur-
press the +/- buttons within 1 minute
4
rent weekday
to set the current weekday. Confirm
with the SEL button
After setting the weekday, press the
+/- buttons to select CTDN and con-
firm with the SEL button. Then, set
Setting the
countdown
the timer's required ON time by
5
pressing the +/- buttons. Press the
timer
SEL button again so that CTDN
appears again
When, after setting the weekday (step
Exit the time
no.4) or the timer, TIME or CTDN
6
or timer set-
appears flashing again, press the +/-
ing
buttons to select EXIT and close with
the SEL button
Note:
When, in programming mode, no button is pressed for 1
minute, the timer will automatically return to normal op-
eration.
If the countdown timer is not required, skip step no. 5.
The countdown timer is started by a momentarily closing
contact connected to M - D1. The N.O. contact across
Q11 - Q14 remains closed until the set time has elapsed.
G5243X1
Countdown
enable
am
pm
5243Z01en
How
Display
T
ME
I
12HR
or
24HR
E.g.
10:30
Su...Sa
CTDN
EX
I
05.05.2003