PFFY-P-VLEM-E/PFFY-P-VLRM-E series
Item
Power source
Cooling capacity*1/Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Fan
Airflow rate (Low-High)
Noise level (Low-High)*6 *7
Filter
Item
Power source
Cooling capacity*1/Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Fan
Airflow rate (Low-High)
Noise level (Low-High)*6 *7
Filter
PDFY-P-VM-E series
Item
Power source
Cooling capacity*1/Heating capacity*1
Height
Dimension*2
Width
Depth
Net weight
Airflow rate (Low-Middle2-Middle1-High) m
Fan
External static pressure*3
Noise level (Low-Middle2-Middle1-High)*5 *7 dB(A)
Filter
Item
Power source
Cooling capacity*1/Heating capacity*1
Height
Dimension*2
Width
Depth
Net weight
Airflow rate (Low-Middle2-Middle1-High) m
Fan
External static pressure*3
Noise level (Low-Middle2-Middle1-High)*5 *7 dB(A)
Filter
PEFY-P-VMS-E series
Item
Power source
Cooling capacity*1/Heating capacity*1
Height
Dimension
Width
Depth
Net weight
Airflow rate (Low-Middle-High)
Fan
External static pressure*4
Noise level (Low-Middle-High)*4 *7
Filter
PEFY-P-VMR-E-L/R series
Item
Power source
Cooling capacity*1/Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Middle-High)
Fan
External static pressure
Noise level (Low-Middle-High)*7
Filter
Notes: * Operation temperature of indoor unit.
Cooling mode: 15 °C WB - 24 °C WB
Heating mode: 15 °C DB - 27 °C DB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27 °C DB/19 °C WB
Heating: Indoor: 20 °C DB
*2 The figure in ( ) indicates panel's.
*3 The external static pressure is set to 50 Pa at factory shipment.
*4 The external static pressure is set to 15 Pa at factory shipment.
*5 The figure in < > indicates noise level at 240 V/50 Hz.
*6 The figures represent a 240 V/50 Hz unit measured at a point which is 1 m away from the front of the unit and at a height of 1 m from the floor.
The noise is approximately 1 dB(A) less for a 230 V unit and approximately 2 dB(A) less for a 220 V unit. The noise is approximately 3 dB(A) less when the
measurement point is 1.5 m away from the front of the unit and at a height of 1.5 m from the floor.
*7 The operating noise is the data that was obtained in an anechoic room.
Model
P20VLEM-E
kW
2.2/2.5
mm
630/1,050/220
kg
23
m
3
/min
5.5-6.5
dB(A)
34-40
Model
P20VLRM-E
kW
2.2/2.5
mm
639/886/220
kg
18.5
3
m
/min
5.5-6.5
dB(A)
34-40
Model
P20VM-E
kW
2.2/2.5
mm
295 (58)
mm
710 (790)
mm
735 (600)
kg
25.5 (5)
3
/min
6.0-6.5-7.5-8.5
Pa
30/50/100
28-30-33-36
Model
P63VM-E
kW
7.1/8.0
mm
295 (58)
mm
1,160 (1,240)
mm
735 (600)
kg
39 (7)
3
/min
12.5-14.0-16.0-18.0
Pa
30/50/100
30-34-36-39
Model
P20VMS-E
kW
2.2/2.5
mm
200
mm
900
mm
700
kg
23
3
m
/min
6-7-8
Pa
5/15/35/50
dB(A)
22-25-27
Model
P20VMR-E-L/R
~220-240V 50Hz/~220-230V 60Hz
kW
2.2/2.5
mm
292/640/580
kg
18
3
m
/min
4.8/5.8/7.9
Pa
5
220V
20/25/30
dB(A)
230V
21/26/32
240V
22/27/30
Outdoor: 35 °C DB
Outdoor: 7 °C DB/6 °C WB
P25VLEM-E
P32VLEM-E
~220-240V 50Hz / ~208V-230V 60Hz
2.8/3.2
3.6/4.0
630/1,050/220
630/1,170/220
23
25
5.5-6.5
7.0-9.0
34-40
35-40
Standard filter
P25VLRM-E
P32VLRM-E
~220-240V 50Hz / ~208V-230V 60Hz
2.8/3.2
3.6/4.0
639/886/220
639/1,006/220
18.5
20
5.5-6.5
7.0-9.0
34-40
35-40
Standard filter
P25VM-E
P32VM-E
~220-240V 50Hz / ~220V 60Hz
2.8/3.2
3.6/4.0
295 (58)
295 (58)
710 (790)
710 (790)
735 (600)
735 (600)
25.5 (5)
27 (5)
6.0-6.5-7.5-8.5
6.0-6.5-7.5-8.5
30/50/100
30/50/100
28-30-33-36
28-30-33-36
Long life filter
P71VM-E
P80VM-E
~220-240V 50Hz / ~220V 60Hz
8.0/9.0
9.0/10.0
295 (58)
295 (58)
1,160 (1,240)
1,160 (1,240)
735 (600)
735 (600)
39 (7)
39 (7)
13.5-15.5-17.5-19.5
14.5-16.5-18.5-21.0
30/50/100
30/50/100
32-35-37-40
34-37-40-42
Long life filter
P32VMS-E
P25VMS-E
~220-240V 50/60Hz
2.8/3.2
3.6/4.0
200
200
900
900
700
700
23
23
6-7-8
7.5-8.5-10
5/15/35/50
5/15/35/50
22-25-27
25-28-30
Standard filter
P25VMR-E-L/R
P32VMR-E-L/R
2.8/3.2
3.6/4.0
292/640/580
292/640/580
18
18
4.8/5.8/7.9
4.8/5.8/9.3
5
5
20/25/30
20/25/33
21/26/32
21/26/35
22/27/30
22/27/33
Standard filter
P40VLEM-E
P50VLEM-E
4.5/5.0
5.6/6.3
630/1,170/220
630/1,410/220
26
30
9.0-11.0
12.0-14.0
38-43
38-43
P40VLRM-E
P50VLRM-E
4.5/5.0
5.6/6.3
639/1,006/220
639/1,246/220
21
25
9.0-11.0
12.0-14.0
38-43
38-43
P40VM-E
4.5/5.0
295 (58)
960 (1,040)
735 (600)
32 (6)
10.0-11.0-12.5-14.0
10.0-11.0-12.5-14.0
30/50/100
34-36-37-39
P100VM-E
11.2/12.5
335 (58)
1,510 (1,590)
775 (600)
52 (8.5)
19.5-28.0
50/100/130
34-42 <37-44>
P40VMS-E
P50VMS-E
4.5/5.0
5.6/6.3
200
200
900
900
700
700
24
24
8-9.5-11
9.5-11-13
5/15/35/50
5/15/35/50
28-30-33
30-32-35
P63VLEM-E
7.1/8.0
630/1,410/220
32
12.0-15.5
40-46
P63VLRM-E
7.1/8.0
639/1,246/220
27
12.0-15.5
40-46
P50VM-E
5.6/6.3
295 (58)
960 (1,040)
735 (600)
34 (6)
30/50/100
34-36-37-39
P125VM-E
14.5/16.3
335 (58)
1,510 (1,590)
775 (600)
52 (8.5)
24.0-34.0
50/100/130
40-45 <42-46>
P63VMS-E
7.1/8.0
200
1,100
700
28
12-14-16.5
5/15/35/50
30-33-36
17