CONFIGURATION LIMITS
Unit configuration must take the following requirements into
account:
if there is a heater you will also need a water probe to
be installed:
if there is a heater and a valve, then the valve must be a
3-WAY (NO 2-WAY VALVES);
if Summer/Winter switching is set on "Auto on water
temp." then there must also be a water probe;
no heater must be installed on 4-pipe units;
with 4-pipe units with a single water probe, summer/
winter switching cannot be set on "Auto on water
temp.";
it is only possible to set summer/winter switching on
"Auto on air temp." if there is an electric heater or if the
unit has 4-pipes;
If SUMMER/WINTER switching is set on "Auto on water
temp." it is not possible to use a 2-way valve. The water
probe must be installed on a point in the hydraulic
circuit with minimum circulation.
FC66003946
Rev 00
Controller for units
USER MANUAL
It is strictly forbidden to reproduce this manual, even partially
CONFIGURABLE DIGITAL OUTPUT
The board has a digital output (identified by O7 on the electrical
diagram) and its status is linked to one of the operating statuses
of the unit reported in the list below:
• Operating mode
• Cooling or heating request
• Cooling request
• Heating request
• ON/OFF status of the unit
• Alarm installed
• Dehumidify call
• Humidify call
• High room temperature
• Low room temperature
• No water consent to heating
• No water consent to cooling
• From supervisor
and selectable from the "DOUT Configuration" configuration
parameter. It is also possible to choose, using the next "Digital
output logic" parameter setting, whether the status of the relay
needs to follow the logic NO (Normally Open) or NC (Normally
Closed).
STAND-BY MODE
If no operation is performed on the user unit keyboard for 30
seconds the main screen goes into stand-by mode, which
can differ based on the settings of the "Stand-by Mode"
parameter, accordingly:
Stand-by mode = Off: the display goes completely
black;
Stand-by mode = Clock: the display goes partly black
and the current time and date are shown;
Stand-by Mode = Temperature: the display goes partly
black and the room temperature and any humidity are
shown, if the probe is installed.
SERIAL CONNECTION FAILURE
If the serial connection fails with the controller set as
SLAVE, FWECSA will either maintain the supervisor on/off
settings and summer/winter mode, or it will reset the last
settings entered from the keyboard, based on the relative
configuration parameter.