PERATION RANGE
LWC
60
55
50
45
40
30
20
a
a
a
b
b
b
ZH
ZH
ZH
10
ZL
ZL
ZL
0
–5
–2
-2 -2
5
32
–10
0
10
20
LWC
Leaving water temperature condenser
LWE
Leaving water temperature evaporator
a
Glycol
b
Water
Continuous operation range
M
AIN COMPONENTS
(refer to the outlook diagram supplied
with the unit)
1
Compressor
2
Evaporator
3
Condenser
4
Switchbox
5
Chilled water in
6
Chilled water out
7
Condenser water out
8
Condenser water in
9
Evaporator entering water temperature sensor
10 Freeze-up sensor
11 Condenser entering water temperature sensor
12 Digital display controller
13 Power supply intake
S
ELECTION OF LOCATION
The units are designed for indoor installation and should be installed
in a location that meets the following requirements:
1
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
2
The space around the unit is adequate for servicing.
3
There is no danger of fire due to leakage of inflammable gas.
4
Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone.
5
Ensure that water cannot cause any damage to the location in
case it drips out of the unit.
The equipment is not intended for use in a potentially explosive
atmosphere.
I
NSPECTING AND HANDLING THE UNIT
At delivery, the unit should be checked and any damage should be
reported immediately to the carrier claims agent.
Installation manual
2
U
NPACKING AND PLACING THE UNIT
1
Cut the straps and remove the cardboard box from the unit.
2
Remove the four screws fixing the unit to the pallet.
3
Level the unit in both directions with the lifting lugs which are
delivered with the control box (ECB*MUCW).
4
Use four anchor bolts with M8 thread to fix the unit in concrete
(directly or using the floor standing supports).
I
MPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:
R410A
(1)
GWP
value:
2090
(1)
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate.
C
HECKING THE WATER CIRCUIT
The units are equipped with water inlets and water outlets for connec-
tion to a chilled water circuit and to a hot water circuit. These circuits
must be provided by a licensed technician and must comply with all
relevant European and national regulations.
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.
Before continuing the installation of the unit, check the following
points:
1
A circulation pump must be provided in such a way that it dis-
charges the water directly into the heat exchanger.
2
A flow switch must be installed in the water outlet pipe to prevent
the unit from operating at a water flow which is too low. A
terminal is provided in the switch box for the electrical
connection of the flow switch.
3
A wire mesh strainer (<1 mm) must be installed at the pump
suction as to protect the pump and the heat exchanger from
foreign matter.
4
Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.
5
Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing.
6
Shut-off valves should be provided at the unit so that normal
servicing can be accomplished without draining the system.
7
Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EIMHP01008-17EU_01