front connection
NOTE
Make sure to close the piping intake hole again after
installation work.
side connection
Cut out the inner part of the conduit hole with a cutter.
bottom connection
I
Liquid side: Bend the liquid side accessory pipe
and connect it to the stop valve. Take care not to
allow it to touch the gas side pipe.
A = bending position for 5Hp
B = bending position for 8/10Hp
Gas side: Cut the gas side accessory pipe and
I
make connection using an elbow (field supply).
A = cutting position for 5Hp
B = cutting position 8/10Hp
2
Make sure to perform the piping installation within the range of
the maximum allowable pipe length, allowable level difference
and allowable length after branching as indicated in "Example of
connection" on page 6.
For installation of the refrigerant branching kit, refer to the
3
installation manual delivered with the kit.
4
Pipe connection
-
Apply ether or ester oil around the flare portions before
connecting.
-
Make sure to flow nitrogen gas through the pipe when
brazing.
5
Protection against contamination when installing pipes
-
Take measures to prevent foreign materials like moisture and
contamination from mixing into the system.
Place
Installation period
More than a month
Outdoor
Less than a month
Regardless of the
Indoor
period
-
Great caution is needed when passing copper tubes through
walls.
CU-5~10MX1SPP
Urban Multi air conditioner
4PW12336-1C
Protection method
Pinch the pipe
Pinch or tape the pipe

Selection of piping material

1
Foreign materials inside pipes (including oils for fabrication)
must be 30 mg/10 m or less.
2
Use the following material specification for refrigerant piping:
-
construction material: Phosphoric acid deoxidized seamless
copper for refrigerant.
-
size: Determine the proper size referring to "Example of
connection" on page 6.
-
The wall thickness of the refrigerant piping should comply
with relevant local and national regulations. For R-407C the
design pressure is 3.2 MPa.
3
Make sure to use the particular branches of piping that have
been selected referring to "Example of connection" on page 6.
4
In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:
-
select the pipe size nearest to the required size.
-
use the suitable adapters for the change-over from inch to
mm pipes (field supply)
Installation manual
5