Fig. 5
Data plate location
LLH / Temperature Sensor resistance values

°F ( °C)
°F ( °C)
46 (8)
25065
100 (38)
57 (14)
19170
111 (44)
68 (20)
14772
122 (50)
79 (26)
11500
133 (56)
90 (32)
9043
144 (62)
Table 5 Measured values from supply temperature sensor (scope of
delivery)
Select additional temperature sensors that may need to be used on the
basis of the information in the technical documentation for the boiler
installed and the CRC100/CRC200 installed.
2.5

Cleaning and care

▶ Wipe the housing with a damp cloth when necessary. Never use
aggressive or acidic cleaning agents for this.
2.6

Additional system components

To create a functional system in which the CZM100 is used, various
components are required:
• Boiler and possibly a IDHW Storage Tank
• CRC100, CRC200
• Accessories
Install boiler, CZM100, modules, CRC100/CRC200 and
supplemental accessories in compliance with legal
regulations and the instructions provided. You can
obtain additional supplemental accessories from your
local dealer.
CRC100/CRC200 (Bosch products)
• CRC100 for simple room temperature-dependent control
– Zone controller for max. 8 zones (one CRC100 per zone required)
– Modulating control of supply temperature
– No time program
– Display of error codes for troubleshooting
– Fixed WWSD Temperature of 70 °F (21 °C)
– Connection to CZM100 via BUS system
• CRC200 for advanced room temperature-dependent control
– Zone controller for max. 8 zones (one CRC200 per zone required)
– Modulating control of supply temperature
– Time schedule program for the individual heating zone assigned
– Backlit digital display
CZM100
6 720 810 538-03.1O


°F ( °C)
7174
154 (68)
2488
5730
165 (74)
2053
4608
176 (80)
1704
3723
187 (86)
1421
3032

Environmental protection/disposal | 5

– Time program for IDHW Tank, if CRC200 is connected to Zone 1,
active 30 min before and after time program of space heating.
– Display of error codes for troublshooting
– Adjustable setting for WWSD (warm weather shut down).
Adjusted through CRC200 connected to Zone 1.
– Connection to CZM100 via BUS system
If CRC200 is connected to Zone 1 and WWSD is
manually adjusted: The new adjusted temperature will
override the rest of the zones in the system even the
factory default of 70 °F (21 °C) in a CRC100.For WWSD
and Weather Compensation Modes an outdoor sensor is
needed as an additional accessory.
Accessories (not included)
• Transformer 24 V AC, (minimum of 30 VA) for systems with zone
valves (to supply power to the low-voltage side of the CZM100)
3
Environmental protection/disposal
Environmental protection is one of the fundamental company policies of
the Bosch Group. We regard quality of performance, economy and
environmental protection as equal objectives.
Environmental protection laws and regulations are strictly adhered to.
To protect the environment, we use the best possible technology and
materials taking into account economic points of view.
Packaging
For the packaging, we participate in the country-specific recycling
systems, which guarantee optimal recycling. All packaging materials
used are environmentally-friendly and recyclable.
Old appliances
Old appliances contain resources that should be recycled.
The components are easy to separate and the plastics are marked. This
allows the various components to be sorted for appropriate recycling or
disposal.
6 720 811 731 (2015/01)

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Czm100

Table des Matières