DIP switch
Definition of DIP Switches
Fan OFF temperature when heating (anti-cold air function)
SW1
• [00]: 24°
• [01]: 15 °C
• [10]: 8 °C
• [11]: Reserved
Behaviour of the fan once the room target temperature has been
reached
SW2
• [0]: Fan off
• [1]: Fan on (anti-cold air function deactivated)
Automatic restart
SW3
• [0]: Automatic restart on (note setting)
• [1]: Automatic restart off (do not note setting)
Set master and slave unit
SW5
• [00]: Master unit only, no slave unit
• [01]: Master unit (heating)
• [10]: Master unit (cooling)
• [11]: Slave unit
Temperature compensation (heating)
SW6
• [00]: 6 °C
• [01]: 2°C
• [10]: 4°C
• [11]: Reserved
1) Default highlighted in bold
Table 195 Definition of DIP Switches
Behaviour of terminals (F2)
F2
Behaviour if contact switch is closed
(As-delivered condition)
• Operation via app/remote control is possible.
• Indoor unit switches on.
• Output signal is on/off, depending on operation via the app/
remote control.
– Off: if indoor unit is switched on.
– On: if indoor unit is switched off.
• Operation via app/remote control is possible.
• Indoor unit switches on.
• Output signal is off.
Table 198 DIP switch F2
"Remote control" means infra-red remote control or room controller.
Climate 5000 M – 6721849819 (2022/09)
1)
Only available for CL5000iL 4C...
DIP switch
Definition of DIP Switches
Default cooling and heating or only cooling
SW7
• [0]: Cooling and heating
• [1]: Cooling only
1) Default highlighted in bold
5.2
DIP switch settings for rack-mounted units
DIP switch
Definition of DIP Switches
ENC3
Network address
F1
Expands the number of possible network
addresses.
F2
Behaviour of terminals (input/output signal).
Table 196 Definition of DIP Switches
Network addresses (F1+ENC3)
The network address must be set in systems in which many indoor units
communicate with one another.
F1
ENC3
Network address
0 - F
0 – 15 (Factory setting)
0 - F
16 – 31
0 - F
32 – 47
0 - F
48 – 63
Table 197 DIP switch F1
Behaviour if contact switch is open
(As-delivered condition)
• Operation via app/remote control is possible. CP appears in
display of indoor unit.
• Indoor unit switches off.
• Output signal is on.
• Operation via app/remote control is possible.
• Indoor unit switches off.
• Output signal is on.
On-site configuration
1)
119