Care And Maintenance - Dennerle 160 Primus Notice D'emploi

Masquer les pouces Voir aussi pour 160 Primus:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 11
1-09588_3076_GA Mehrweg_Primus_Quantum_0915_Layout 1 29.09.2015 15:30 Seite 16
Too much CO
CO
2
KH 6,3 6,4 6,5 6,6 6,7 6,8 6,9 7,0 7,1 7,2 7,3 7,4 7,5
2
32
25
2
16
13
3
48
38
3
24
19
4
64
51
4
32
25
5
8
63
5
4
32
6
96
76
6
48
38
7
111 89
7
56
44
8
127 1 1 8
64
51
9
143 114 9
72
57
10 159 126 1
8
63
11 175 139 111 88
7
12 191 152 121 96
76
13 2 7 164 131 1 4 82
14 223 177 141 112 89
CO
-content in mg/l
2

5 Care and maintenance

5.1 Replace the CO
cylinder
2
Empty cylinder: Close cylinder valve. Unscrew coupling ring
using 27 mm spanner and screw pressure reducer onto refilled
reusable CO
cylinder. Open cylinder valve The bubble count
2
setting will be retained.
Full cylinder: Close cylinder valve. Turn setting knob of pressure
reducer towards " + " as far as it will go, in order to release any
residual pressure in the pressure reducer (if a solenoid valve is
connected, it must be open for this purpose). Unscrew coupling
ring using 27 mm spanner and screw pressure reducer onto re-
filled reusable CO
cylinder. Open cylinder valve Reset number
2
of bubbles.
Always close the cylinder valve in order to shut down the CO
supply for a prolonged period. Unscrew the pressure reducer
when the cylinder is to remain out of use for a prolonged period.
5.2 Testing the CO
backflow check valve
2
The check valve protects your valuable pressure reducer/solenoid
valve from corrosion caused by back-flowing water. As dirt particles
may collect on the sealing surfaces over the course of time, the back-
flow check valve should be checked at least once a year and replaced
every 2-3 years for safety's sake.
Tip: Install a transparent test hose temporarily between backflow
check valve and pressure reducer/solenoid valve and shut down the
CO
supply for 24 hours (close pressure reducer/solenoid valve). If
2
there is water in the test hose after this 24-hour period, this indicates
a leak on the backflow check valve.
The opening of the check valve can only be tested with CO
nimum pressure of approx. 0.3 bar is required to open the valve. It
is not possible to "blow through" the valve with your mouth.
Important note: Use only check valves designed for use with CO
as the special CO
check valve from Dennerle. Standard air check val-
2
correct
Not enough CO
2
2
pH
1
8
6
5
4
3
3
15
12 1
8
6
5
4
2
16 13
1
7
6
5
25
2
16
13
1
8
6
3
24 19
15
12
1
8
35
28 22
18
14
11
9
4
32 25
2
16
13
1
45
36 29
23
18
14
11
5
4
32
25
2
16
13
55
44 35
28
22
18
14
6
48 38
3
24
19
15
65
52 41
33
26
21
16
7
56 44
35
28
22
18
, as a mi-
2
, such
2
ves may become brittle through contact with CO
space of time, resulting in leaks.
Corrosion damage on the pressure reducer/solenoid valve
as a result of water entering into the device is excluded
2
from the guarantee coverage.
3
4
5
5.3 Replacing the washer
6
We recommend replacing the washer (art. no. 3056) in the adapter
7
for connection to reusable cylinders on a regular basis, in order
8
9
to rule out leaking cylinder connections at all times.
1
There is a Longlife washer in the connection socket of the pressure
11
reducer. It is not normally necessary to replace this washer du-
12
13
ring the service life of the pressure reducer. The seal can only be
14
replaced using special tools: Please send in the pressure reducer
to Dennerle's Customer Service department.
5.4 Cleaning and recalibrating the needle valve
There is a factory-calibrated needle valve in the hose connector of the
pressure reducer.
Should no CO
be supplied although the cylinder is full and the setting
2
knob is turned to fully open position, this indicates that the needle
valve is probably blocked. In this case:
Open the valve by turning by one half-turn in anti-clockwise di-
rection using a fine screwdriver (blade format 2 – 2.5 x 0.5 mm),
then "flush" with CO
fully open position.
Important: Do not unscrew valve completely ©
Close valve again by one half-turn.
The valve is factory-set to approx. 120 bubbles per minute when
2
the setting knob is in fully open position. If necessary, it can be
recalibrated by carefully screwing it in or out in steps of approx.
1/8 of a turn.
5.5 Removing the CO
After prolonged service, the CO
to the connector of the pressure reducer and other CO
To remove the hose, it is best to lever it off using a small screwdriver.
Do not pull the hose off by force or cut it open with a knife, as
this may cause damage to the hose connectors ©
5.6 Clean CO
Flipper
2
collector by pulling straight up. ©
Remove CO
2
Place the Flipper flat in your hand so that the suction clips are
pointing to the right. Slide front side panel of the Flipper up-
wards by approx. 2 cm. ©
Fold out side panel. ©
hose, do not pull out. ©
Take out CO
2
Clean all parts with warm water and a soft sponge. Do not use
any cleaning agents.
Re-assemble Mini-Flipper via the reverse procedure.
within only a short
2
for a few seconds with the setting knob in
2
29
hose
2
hose may be very firmly attached
2
equipment.
2
30
31
32
33
34
17

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

300 quantum600 quantum

Table des Matières