11. Trouble shooting / 12. Storage, disposal
Failure
No output signal
No display value
No/False output signal
Output signal unchanged after change
in pressure
Abnormal zero point signal
Signal span too small
Signal span too small
Signal span drops off
Signal span dropping off/too small
In case of unjustified reclamation we charge the reclamation handling expenses.
If the problem persists, contact our sales department. Purge / clean dismounted instruments before
returning them in order to protect our employees and the environment from any hazard caused by
adherent remaining media.

12. Storage, disposal

When storing or disposing of the pressure switch, take precautions with regard
!
to remaining media in removed pressure switches. We recommend cleaning
the pressure switch properly and carefully. Remaining media in the pressure
Warning
port may be hazardous or toxic!
Disposal
Dispose of instrument components and packaging materials in accordance with the
respective waste treatment and disposal regulations of the region or country to which the
instrument is supplied.
tecsis reserves the right to alter these technical specifications.
38
Betriebsanleitung / Operating manual / Instructions de service / Instrucciones de uso
Possible cause
Cable break
No/incorrect voltage supply
Incorrectly wired
Mechanical overload through
overpressure
Overload limits exceeded
Mechanical overload through overpres-
sure
Power supply too high/too low
Moisture present (e.g. at the cable tail) Install the cable correctly
Diaphragm is damaged, e.g. through
impact, abrasive/agressive media;
corrosion of diaphragm/pressure
connector; transmission fluid missing.
Procedure
Check connections and cable
Adjust the voltage supply to correspond
with the Operating Instructions
Follow pin assignment (see Instrument
Label / Operating Instructions)
Replace instrument; if failure reoccurs,
consult the manufacturer
Ensure permissible overload limits are
observed (see Operating Instructions)
Replace instrument; if failure reoccurs,
consult the manufacturer
Correct the power supply in line with
the Operating Instructions
Contact the manufacturer and replace
the instrument