Wilo RAIN3 Notice De Montage Et De Mise En Service page 36

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 46
en
Menu no.
Parameter /
info
Sensor
5.11
range pres-
sure
Sensor
5.21
range level
cistern
Level sensor
5.22
installation
height
High water
5.24
on threshold
cistern
Cistern
5.26
shape
Cistern high/
diameter
5.29
Pump kick
5.40
Pump kick
5.42
interval
PUmp kick
5.43
duration
Over flow on
5.51
threshold
cistern
Tap water
5.52
on threshold
cistern
Rain water
5.53
on threshold
cistern
Calcination
5.54
protection
System
5.55
flushing
Flushing
5.56
duration
Max. run-
ning time
5.57
pump
Fault mes-
5.59
sage beha-
vior
Minimum
5.61
pressure
Delay dry
5.62
run protec-
tion
36
Description
Min.
Max. Text
0.0
16.0
0.0
25.0
1
1000
1
1000
none; rectangle -
cylindric; cylindric
horizontal - sphere
1
1000
1
336
1
60
1
1000
1
1000
1
1000
0
7
1
31
1
9
0
360
Raise - Fall
0.7
1.0
1
180
Default
Unit
Ac-
cess
level
10.0
bar
3
5.00
m
3
15
cm
3
<5.51>+5
cm
3
rectangle
2
110
cm
3
Off; on
2
24
h
2
5
s
2
100
cm
3
<5.22> +10
cm
2
<5.22> +10
cm
2
7
d
2
7
d
2
3
min
2
0
min
2
Fall
2
1.0
bar
2
15
s
2
Description
Defines the range of the installed analog
pressure sensor
Defines the range of the installed sensor
in cistern
Distance between ground level and in-
stalled height of sensor
The level threshold in cistern above high
water is reported (distance refer to 5.51)
5.22 < 5.51 < 5.24 < 5.29
If cistern has a defined shape it can be
selected here and can be used to calcu-
late volume capacity of the water
If a shape cylindric horizontal or sphere
for cistern is selected that is required a
diameter it is defined here for calculate
volume capacity 5.22 < 5.51 < 5.24 <
5.29
Enable or disable pump kick functionality
The interval between pump kicks or after
pumps have stopped until the next pump
kick
The time which pump is running during
pump kick
The level threshold in cistern above over-
flow is reported. 5.22 < 5.51 < 5.24 <
5.29
The level threshold below which to
switch to TWM (distance refer to 5.22)
5.22 < 5.52 < 5.53 < 5.51
The level threshold above which to
switch to RWM (distance refer to 5.52)
5.22 < 5.52 < 5.53 < 5.51
To protected the valve against calcina-
tion it can be operate from time to time
as defined in this parameter
To clean up the break tank once in a
while it can be flushed with fresh water
after period defined here
Time which pump has to run totally in
TWM for the next pump operations. After
this time RWM are possible again.
Pump should no longer run than the
timespan defined here or else an alarm is
generated; 0s means unlimited running
time and no alarm message
zero- or one-signal in case of failure
The pressure threshold below which a dry
running is detected
The delay to detect dry run. It avoids false
dry run detection by short impulse on the
input
WILO SE 2020-02