Voltage
Maximum running current (A)
Minimum wiring size
Control port signal type
For outside circulation pump P_o and outside
solar energy pump P_s:
10
22
CN11
Power supply
7 5 3 1
A1
KM2
A2
8
6
4
2
outside circulation pump P_o
CN11
Power supply
7 5 3 1
A1
KM8
A2
8
6
4
2
outside solar energy pump P_s
Voltage
Maximum running current (A)
Minimum wiring size
Control port signal type
a) Procedure
Connect the cable to the appropriate terminals as
shown in the picture.
Fix the cable with cable ties to the cable tie mountings
to ensure stress relief.
220-240VAC
0.2
0.75
Type 1
25 26
27 28
1 2 3 4 5
29 30 31 32
6 7 8 9 10
CN7
CN30
11
P_s
23
N
220-240VAC
0.2
0.75
Type 2
10) For smart grid:
The unit has smart grid function, there are two ports on PCB to
connect SG signal and EVU signal as following:
CN21
CN5
CN28
CN32
CN29
CN25
CN42
CN40
DIS1
CN41
S3
S4
CN22
CN1
CN2
1
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
CN11
1. When EVU signal is on , and SG signal is on, as long as the DHW
mode is set to be valid, heat pump will operate DHW mode priority and
the DHW mode setting temperature will be changed to 70ºC. T5<
69ºC, the TBH is on,T5≥70ºC,t he TBH is off.
2. When EVU signal is on , and SG signal is off, as long as the DHW
mode is set to be valid and the mode is on, heat pump will operate
DHW mode priority. T5<T 5S-2,t he TBH is on,T5≥T5S+3,t he
TBH is off.
3. When EVU signal is off, and SG signal is on, the unit operates
normally.
4. When EVU signal is off, and SG signal is off, the unit operates as
below: The unit will not operate DHW mode, and the TBH is invalid,
disinfect function is invalid. The max running time for cooling/heating is
"SG RUNNING TIME", then unit will be off.
48
CN8
CN6
S1
S2
CN4
SW9
CN17
11
12
25
26
27
28
1
2
3
4
22
23
24
29
30
31
32
6
7
8
9
CN7
CN30
V.1
CN24
CN16
CN13
CN15
CN18
CN31
CN35
CN36
5
10