46. Maximum discharge temperature
47. Overheat protection
50. Installation height
60. Function of inputs
V
O
ALUE
PTION
0
No function
1
Unit off locally – NO
6
Heating off
9
Release – NO
en-60
The discharge temperature is limited by the controller to a
maximum of 50 °C. Possibly set a lower value in order to save
energy.
If the actual room temperature becomes higher than the pre-
set room temperature, the heating can be switched off in
order to prevent the room from becoming too warm.
Set the temperature above which the heating must be disabled.
Note:
n
This function can only be used if the unit is set to
automatic.
Note:
n
If this function is activated, then function
air temperature
In order to use the auto-active control as efficiently as possi-
ble and with minimum energy consumption, it is necessary to
set the installation height of the unit correctly.
Note:
n
Use values in metres.
The installation height is the distance from the floor to the
underside of the unit (h).
The unit has three inputs (terminal block X520) which can be
used to enable a function to be controlled by an external
accessory such as a thermostat or a signal from a building
management system.
Values for inputs 1 and 2
D
ESCRIPTION
The input has no function.
The unit is switched OFF when the contact is closed. (This only
works with the units to which the input signal is directly connected
(locally).)
The heating is switched OFF when the contact is closed.
The user is allowed to switch the unit on and off when the contact
is closed.
C
A
OMFORT
IR
6. Minimum
is ignored.
C
URTAIN