Gradual door response: the unit responds to the opening
and closing of the door. The speed of response is based on
the open/closed ratio.
Note:
n
With the door closed, the unit can be set to keep
the room at a minimal room temperature.
Note:
n
In some situations the unit is not active, even though
it is on.
1.3.4 i-sense infra red technology
The i-sense infra red technology makes it possible to use the
automatic CHIPS control without adding external controls
such as an outdoor temperature sensor and a door contact
switch.
Next to the discharge grille is an IR sensor which measures
the temperature in a strip of 8 planes perpendicular to the
door opening. As a result, the sensor provides the controller
with diverse information:
Note:
n
The temperature of a floor surface changes gradually.
indoor temperature (T8)
outdoor temperature (lowest measured value of T1, T2
and T3)
Note:
n
An outdoor temperature is only measured if the IR
sensor recognises the door as being open.
door position
If the difference between T5 and T1, T2 or T3 is at least
3°C is, it is assumed that the door is open.
Note:
n
An outdoor temperature can only be recognised if
the unit is on and climate separation is active.
signal for quick start or 30 minutes on (T7 and T8)
If the measured value briefly changes, it is assumed that
someone is walking below the sensor.