 Piping materials and sizes
Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and
Ø12.7 mm, with a wall thickness of 1.0 mm for Ø15.9 mm, with a wall thickness of 1.2 mm
for Ø19.1 mm, and with a wall thickness of 1.0 mm for Ø28.6 mm (half hard).
Do not use any copper pipes with a wall thickness less than these thicknesses.
Pipe side
 Branch pipe
Now the refrigerant pipe is installed using branch pipes supplied as accessories.
Bend and adjust the refrigerant piping so that the branch pipes and pipe after branching
become horizontal.
Fix the branch pipes onto a wall in a ceiling or onto a column.
Provide a straight pipe longer than 500 mm in length as the main piping of the branches.
Correct
Horizontal
Incorrect
Inclination
 Air Purging
For the complete information, read the installation manual for outdoor units of air
conditioner.
Branch pipe
Gas side
Liquid side
Correct
Horizontal
Incorrect
Inclination
6
In parentheses ( ) are wall thickness
Main piping
Branch piping
Main piping
Branch piping
Ø28.6 (half hard 1.0)
Ø15.9 (1.0)
Ø12.7 (0.8)
Ø9.5 (0.8)