Grid Monitoring - ABB PVS800 Manuel D'exploitation

Masquer les pouces Voir aussi pour PVS800:
Table des Matières

Publicité

12
No.
Name/Value
ON
42.18
MPPT P RAMP UP
1...6000%/min
42.19
POWER STOP
RAMP
1...1200%/s

44 GRID MONITORING

44.24
GRIDMON INPUT
SEL
POS SEQ VOLT
RMS VOLT
46 POWER LIMITATION
46.01
UF PLIM MODE
SEL
OFF
INCREMENTAL
46.02
UF PLIM RET
DELAY
0...3600 s
46.03
UF PLIM RET
RAMP
0...3600 s
46.04
UF PLIM RET
FREQ
[46.05] ... 65 Hz
Update notice
FbEq
Description
1
The maximum increase rate of active power is defined by
parameter
42.18 MPPT P RAMP
Defines the maximum increase rate for active power in the MPPT
mode.
1 = 1%/
Maximum increase rate for active power in the MPPT mode.
min
Defines the stopping ramp rate for active and reactive power in a
controlled stop. A controlled stop means that the inverter is
stopped without a fault.
Both active and reactive power are ramped down to zero using this
ramp rate before the inverter is totally stopped.
100 =
Ramp rate. 100%/s equals parameter 04.06 NOMINAL POWER in
1%/s
one second.
Parameters related to internal grid monitoring.
Note: Group 44 is write-protected. It can be write-enabled by
giving a password with parameter 16.03 PASS CODE.
Selects the input for grid voltage monitoring.
0
Grid monitoring for undervoltage and overvoltage is based on the
positive sequence component of the grid voltage.
1
Undervoltage detection is based on the minimum RMS value and
overvoltage detection on the maximum RMS value of the grid
voltage.
The selection between phase-to-neutral and phase-to-phase
voltages is done with parameter 40.24 RMS VOLTAGE CALC.
Parameters for active power limitation during a grid
underfrequency situation.
Enables or disables active power limitation during a grid
underfrequency situation.
0
Active power limitation during a grid underfrequency situation is
disabled.
1
Active power limit increases according to the grid underfrequency
characteristic curve, but decreases only when the grid frequency
has been greater than
46.02 UF PLIM RET
done with a ramp rate defined by parameter
RAMP.
Defines the return delay for a grid underfrequency situation. The
grid frequency has to be greater than
for the duration of this delay before return ramping can be started.
20 = 1 s
Return delay
Defines the ramp rate for decreasing the active power limit after a
grid underfrequency situation.
20 = 1 s
Ramping time from zero to 04.06 NOM AC POWER
Defines the return frequency for a grid underfrequency situation.
100 =
Return frequency
1 Hz
UP.
46.04 UF PLIM RET FREQ
DELAY. Decreasing the active power limit is
46.03 UF PLIM RET
46.04 UF PLIM RET FREQ
Def
6000%/
min
100%/s
POS SEQ
VOLT
OFF
for longer than
300 s
300 s
50.0 Hz
T
R
R
R
R
R