6. Commissioning, operation
Voltages greater than 50 VAC or 75 VDC:
- Do not connect circuits simultaneously with extra-low voltage circuits or with
safety extra-low voltage (SELV) or protected extra-low voltage (PELV).
- Circuits must offer a device, external to the measuring instrument, that
EN
enables the instrument to be isolated from the electrical supply. This must be
easily accessible and be marked as the isolation device for the instrument.
- Cables for the circuit must fulfil the isolation requirements and conform to, for
example, IEC 60227 or IEC 60245.
With flexible connecting cables, use isolated end splices.
Connecting cables must be suited to the ambient temperature range of the
application.
Seal the cable entry with the appropriate approved cable glands.
Cable socket design
96
M20 x 1.5
Install the connection cables securely.
26
Only use cable
with a diameter of
7 ... 13 mm
WIKA operating instructions DPGS40TA with component testing