5.5.1.5 Examples
examples of settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 St.-alone mode
off
DS-1 St.-alone mode
off
Step1, Example 1 (factory
Step1, Example 2:
setting):
8, 7, 6 AC-in: 50A
8, 7, 6 AC-in: 50A
5 AES: off
5 AES: off
4, 3 Charging current: 75%
4, 3 Charge: 100%
2, 1 Stand-alone mode
2, 1 Stand-alone
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
switches, see appendix A, position K). The overload and low-battery LED's will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
5.5.2 Step 2: Other settings
The remaining settings are not relevant (na) for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
voltage
oltage
14.1
13.8
off
off
28.2
27.6
56.4
55.2
14.4
13.8
off
on
28.8
27.6
57.6
55.2
14.7
13.8
on
off
29.4
27.6
58.8
55.2
15.0
13.8
on
on
30.0
27.6
60.0
55.2
ds6: absorption time 8 or 4 hours (na for L2, L3)
ds5: adaptive charging characteristic (na for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (na for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Note:
-
If "adaptive charging algorithm" is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If "adaptive charging algorithm" is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
DS-8
on
DS-8
DS-7
on
DS-7
on
DS-6
on
DS-6
on
DS-5
off
DS-5
DS-4
on
DS-4
on
DS-3
on
DS-3
on
DS-2
off
DS-2
DS-1
off
DS-1
Step1, Example 3:
8, 7, 6 AC-in: 16A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
Storage
voltage
13.2
Gel Victron Long Life (OPzV)
26.4
Gel Exide A600 (OPzV)
52.8
Gel MK battery
Gel Victron Deep Discharge
13.2
Gel Exide A200
26.4
AGM Victron Deep Discharge
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.2
Tubular plate traction batteries in
26.4
semi-float mode
52.8
AGM spiral cell
13.2
Tubular plate traction batteries in
26.4
cyclic mode
52.8
on = 8 hours
on = active
on = active
on = active
on = 230V
on = 50Hz
off
DS-8
on
DS-7
on
DS-6
off
off
DS-5
on
DS-4
off
DS-3
on
off
DS-2
off
off
DS-1
off
Step1, Example 4:
8, 7, 6 AC-in: 30A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
Suitable for
off = 4 hours
off = inactive
(inactive = fixed absorption time)
off = inactive
off = inactive
off = 240V
off = 60Hz