INSTRUC T ION SHEET
GN2000-M - 200 Amp conversion kit for ground
on neutral in meter sockets BQ2 & BS2
WARNING:
Risk of shock, disconnect
power before installation
Figure 1
Installation Instructions
1. Confirm that the meter socket is identified IN.
2. Remove the line and the load side conductors.
3. Remove the main block by removing the (2) mounting screws identified in Figure 1. Keep the block and discard the screws.
4. Remove and discard the material covering the center hole in the enclosure (Figure 2).
5. Thread the hole in the center of the enclosure by inserting the 1/2" screw supplied in the kit (Figure 2). Apply a maximum tightening
torque of 50 IN.LB.
6. Remove the 1/2" screw once the thread has been formed. Discard the 1/2" screw.
7. Remove the neutral connector by unscrewing the screw under the main block. Keep the block and discard the neutral connector, the
screw and the flat washer (Figure 3).
8. Reinstall the main block in position using the guides in the backside of the enclosure and tighten the (2) yellow 3/4" screws supplied in
the kit. Apply a torque of 35 IN.LB. (Figure 1).
9. Insert the neutral assembly supplied in the kit making sure to position it as shown in Figure 4.
10. Insert the 1-7/8" screw supplied in the kit in the center of the assembly. Apply a maximum tightening torque of 50 IN.LB. (Figure 4).
11. Connect the conductors on the line and load side and apply the tightening torque indicated on the meter socket label.
tnb.abb.com
(US/Latin America)
tnb.ca.abb.com
(Canada)
abb.com
Warranty:
tnb.abb.com/ecpwarranty
Figure 2
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.
IMPORTANT
Read and understand all instructions and
safety information before use. Be aware
of proper usage and potential hazards.
CAUTION: Product should be installed
by a qualified electrician in accordance
with national and local electrical codes.
Figure 3
We reserve all rights in this document and
in the subject matter and illustrations
contained therein. Any reproduction
– in whole or in part – is forbidden without
prior written consent of ABB.
© 2022 ABB. All rights reserved.
Figure 4