LoRaWAN PULSE - Mode d'emploi / User guide version V1.6.1

4.1.2 Downlink

Payload downlink max = 8 bytes, data format : Little endian, low significant byte first.
Bytes
0
Code
ATS registre
Value
0x03
Note
ATS register
Value
0x04
Note
ATS register
Value
0x05
Note

4.1.3 Status

Product status.
Low bat error = 1 if supply voltage <= 2.5 V, else 0
Configuration switch error = 1 if no switch consistency, else 0
HW error = 1 if hardware failure, else 0
Configuration done = 1 if last downlink frame was a right frame and configuration done, else 0
Alarm/Status
Bit7
Frame counter
No error
Low bat error
Configuration
Switch error
HW error
Configuration
done
1
2
S299
S298
0 to 43200
Device type
Transmit period (s)
S294
0 to 65535
Pulse 1 width (0.1 dm3, 0.1L
or 1 W.h)
S292
0 to 65535
Pulse 2 width (0.1 dm3, 0.1L
or 1 W.h)
Bit6
Bit5
0x0 à 0xF
3
4
PAYLOAD
S297
0 to 3
Channel On/
Off
S293
0 to 2
Pulse 1 memo index
S291
0 to 2
Pulse 2 memo index
Bit4
Bit3
HW
0
0
0
1
0
5
6
S296
S295
0 to 12
0 to 12
Channel 1
Channel 2
Type
Type
-1
32
32
-1
Bit2
Bit1
Switch
Low bat
0
0
0
1
1
0
0
0
0
0
7
S290
O to 2
Pulse input
Type
S296
0 to 12
S295
0 to 12
Bit0
Configuration
0
0
0
0
1