Translation of the original instructions
Settings and Troubleshooting
CONFIGURATION
To enter the procedure:
make sure no processes are in progress
press UP ( ) and DOWN ( ) for 4 s: "PA" appears on the display
press SET ( )
press UP ( ) or DOWN ( ) within 15 s to set "-19"
press SET ( ) or wait for 15 s
press UP ( ) and DOWN ( ) for 4 s: "SP" appears on the display.
To select a parameter:
press UP ( ) or DOWN ( )
To modify a parameter:
press SET ( )
press UP ( ) or DOWN ( ) within 15 s
press SET ( ) or wait for 15 s.
To exit the procedure:
press UP ( ) and DOWN ( ) for 4 s or wait for 60 s.
Turn off the instrument after modifying the parameters.
ALLARMS AND ERRORS
CODE TYPE OF ALARM
Solutions
Consequences
iA
MULTIFUNCTION INPUT ALARM
Verify what caused the input activation / See the i5 and i6 parameters
Effect established by the i5 parameter / Alarm output activated with u1=3
iSd
PRESSURE SWITCH ALARM
Verify what caused the input activation / See the i5, i6, i7, i8 and i9 parameters /
Switch the instrument off and on again or disconnect the power supply
The regulators go off / Alarm output activated with u1=3
COH
OVERHEATING CONDENSER ALARM
Verify the condenser temperature / See C6 parameter
Alarm output activated with u1=3
CSd
COMPRESSOR BLOCKAGE ALARM
Verify the condenser temperature / See the C7 parameter / Switch the instrument
off and on again: if the condenser temperature is still > parameter C7 when it is
switched on again, disconnect the power supply and clean the condenser
The evaporator compressor and fan go off / Alarm output activated with u1=3
Pr1
CHAMBER SENSOR ERROR
Verify the type of sensor / Verify the integrity of the sensor / Verify the
instrument-sensor connection / Verify the chamber temperature
Compressor on or off for 10 m / Defrosting will not be activated / Relè alarm
activated if u1=3 / Door resistors off if u1=4 / Disabling evap. valve if u1=5
Pr2
EVAPORATOR SENSOR ERROR
Verify the type of sensor / Verify the integrity of the sensor / Verify the
instrument-sensor connection / Verify the evaporator sensor temperature
Defrosting activated for 30 min with P3=1 / Defrosting at intervals with
P3=1 and d8=2 / The evaporator fan operates in parallel with the
compressor with F0=3 or 4 / Alarm output activated with u1=3
Pr3
CONDENSER SENSOR ERROR
Verify the type of sensor / Verify the integrity of the sensor / Verify the
instrument-sensor connection / Verify the condenser sensor temperature
Condenser overheating alarm ("COH") will not be activated / Blocked
compressor alarm ("CSd") will not be activated / Alarm output activated if u1=3
rtc
CLOCK ERROR
Set the date and time
Defrosting at intervals with d8=3; The HACCP will not provide information
regarding the date and time when the alarm was triggered / The Energy
Saving function is not available in real time / Alarm output activated if u1=3
Once the cause that triggered the alarm is resolved, the instrument
restores normal operation, except for the following alarms that require:
• "PF"
any button to be pressed;
• "iSd"-
the instrument to be switched off or the power supply to be
disconnected
• "CSd"
the instrument to be switched off or the power supply to be
disconnected
FAULT
The following items will help you find possible solutions to some
troubles the unit could be subject to. It is understood that the
information given here does not cover all possible cases.
Whenever a safety device triggers, it means that there is a
malfunction; before resetting it, check and remove the cause.
After making the above checks, if the fault persist contact your after-
sales service. Remember to specify the nature of the defect, the
appliance's code and serial number(you will find on its nameplate).
PROBLEM
Possible cause
What to do
1
APPLIANCE DOESN'T START
1.1
Appliance isn't connected to the power supply
Check that the plug is fitted into the mains power supply socket correctly.
2
COMPRESSOR RARELY STOPS
2.1
Room temperature is too high
Ensure proper ventilation to the room
2.2
Refrigerated cabinet condenser is dirty
Check it on a regular basis and clean it thoroughly.
2.3
Low refrigerant charge
Call an authorised technical support centre to find and repair any
leaks and to recharge the compressor with refrigerant.
2.4
Door gaskets do not ensure proper seal
Call an authorised technical support centre to perform the
necessary replacement
2.5
Frost build-up on the evaporator
Do not place hot or high water content foodstuffs into the
appliance and, if needed, perform a manual defrost cycle
2.6
Evaporator motor fan(s) damaged
Call an authorised technical support centre to perform the
necessary replacement
3
OVERFLOWING OF SELF-EVAPORATING CONDENSATE TRAY
3.1
Hot or high-water content foodstuffs are being introduced into the
appliance too often.
Do not introduce hot or high water content foodstuffs into the appliance
3.2
Doors and/or drawers are opened too often.
Pay attention to the conditions of use of your appliance
4
COMPARTMENT TEMPEATURE TOO HIGH
4.1
Refrigerated cabinet condenser is dirty
Check it on a regular basis and clean it thoroughly.
4.2
Feeble aeration of the zone around the technical compartment.
Remove any obstructions for a correct airflow
4.3
Hot air entering the compartment.
Check the correct closure of the door and the gasket to be proper.
If it's not possible to adjust functioning, call a technical support
centre to perform replacement and regulations
4.4
Frost build-up on the evaporator
Perform a manual defrost cycle
ENGLISH 7
7