Télécharger Imprimer la page

Gree GUD35ZD/A-T Manuel Du Propriétaire page 65

Publicité

Les langues disponibles

Les langues disponibles

scales shall be available and in good working order. Hoses shall be complete
with leak-free disconnect couplings and in good condition. Before using the
recovery machine, check that it is in satisfactory working order, has been
properly maintained and that any associated electrical components are sealed to
prevent ignition in the event of a refrigerant release. Consult manufacturer if in
doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant Waste Transfer Notice arranged. Do
not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they
have been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant. The evacuation process shall be
carried out prior to returning the compressor to the suppliers. Only electric
heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
5.5 After-Sales Services
Any quality or other issues encountered in the purchased air conditioner,
please contact the local Gree after-sales service department.
DC Inverter U-match Series Floor Ceiling Type Unit
61

Publicité

loading