DC Inverter U-match Series Floor Ceiling Type Unit
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
Model
Indoor
220-240V 1N~50Hz
unit
208-230V 1N~60Hz
Model
GUD35W/NhA-T
GUD50W/NhA-T
GUD71W/NhA-T
GUD85W/NhA-T
GUD100W/NhA-T
GUD125W/NhA-T
GUD140W/NhA-T
GUD100W/NhA-X
GUD125W/NhA-X
GUD140W/NhA-X
GUD160W/NhA-X
NOTICE:
① Fuse is located on the main board.
② Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to
be plugged or unplugged.
③ Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
④ Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40℃ and multi-core
copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath)
is protected by a conduit, and is resistant to 90℃ in maximum (See IEC
60364-5-52).If
specifications according to national standards.
Power supply
V/Ph/Hz
Power supply
V/Ph/Hz
220-240V 1N~50Hz
208-230V 1N~60Hz
380-415V 3N~50Hz/60Hz
working
Circuit
Fuse
breaker
capacity
capacity
A
3.15
Circuit
breaker
capacity
condition
changes,
34
Min. sectional
area of power
cord
A
mm
6
1.0
Min. sectional
area of power
cord
A
mm
16
1.5
16
1.5
20
2.5
25
2.5
32
4.0
32
4.0
40
6.0
16
1.5
16
1.5
16
1.5
16
1.5