Code for voltage and No. of poles
acc. to UL
Voltage
2-pole + PE
125V 60Hz
230V 400Hz
250V 60Hz
480V 60Hz
3-pole + PE
600V 60Hz
480V 60Hz
250V 60Hz
230V 400Hz
125/250V 60Hz
3-pole + N + PE
600V 60Hz
277V 60Hz
230V 400Hz
120/208V 60Hz
Dimensions in mm
X = fixing dimensions
Wall socket 3-pole
Wall socket 4-pole and 5-pole
2 2 2 2 2
Cooper Crouse-Hinds GmbH
Annex to operating instructions
Annex to operating instructions
Annex to operating instructions
Annex to operating instructions
Annex to operating instructions
Plug and socket system 20A, GHG 511
1
Technical data
1.1
Plug and socket GHG 511
Explosion catagory:
for USL
for CNL
Certifications and Compliances:
for USL
for CNL
Rated voltage:
Clock
3-pole
Colour face
4-pole
(PE)
5-pole
yellow
4 h
Rated current:
light blue 2 h
Back-up fuse:
blue
6 h
without thermal protection
red
7 h
with thermal protection
Switching capacity 3-pole:
Switching capacity 4-pole:
black
5 h
Switching capacity 5-pole:
red
7 h
Perm. ambient temperature:
blue
9 h
Special versions permit deviating temperatures.
light blue 2 h
Perm. storage temperature in original packing:
orange 12 h
Protection category acc. to EN 60529/IEC 529
with closed and secured hinged cover as well
as combinations properly plugged together
black
5 h
Insulation class acc. to EN 60598/IEC 598:
red
7 h
Cable entry: (catalogue version)
light blue 2 h
Wall socket
blue
9 h
plug
plug
plug
Supply terminal:
Wall socket
Flange socket
Plug
Test torques:
Cover screws
Terminals wall-; flange socket
Terminals plug
Self-cutting screws size 4
Self-cutting screws size 5
Weight:
Wall socket
Plug
Flange socket
Wall socket
Plug
Flange socket
Wall socket
Plug
Flange socket
Auxiliary contact:
Rated voltage:
Rated current:
1P + N +
3-pole
4-pole
5-pole
3-pole
GHG 511 43
3-pole
GHG 511 73
3-pole
GHG 511 83
4-pole
GHG 511 44
4-pole
GHG 511 74
4-pole
GHG 511 84
5-pole
GHG 511 45
5-pole
GHG 511 75
5-pole
GHG 511 85
W
W
4h
1P + N +
5h
Arrangement of contact tubes - Series II
AEx de II C T6 / T5
Ex de II C T6 / T5
Class I, Zone 1 and 2
Class I, Division 2 -
Groups A, B, C and D
Class II, Division 2 -
Groups F and G
Class I, Zone 1 and 2
Class I, Division 2 -
Groups A, B, C and D
Class II, Division 1 -
Groups E, F and G
up to 480 V, 60 Hz
up to 600 V, 60 Hz
up to 480 V, 60 Hz
max. 20 A
max. 20 A
max. 35 A gL
277 V / 3 HP, 60 Hz
600 V / 10 HP, 60 Hz
600 V / 10 HP, 60 Hz
-20° C to + 40° C
-55° C to + 80° C
IP 66 (catalogue version)
I - is complied with by the devices
2x M20, (1x hub M20/1/2"NPT, 1x blanking plug)
Ø 8 - 19 mm
Ø 8 - 21 mm
Ø 12 - 21 mm
Cross section
Stripped wire length
2 x AWG 16 - 12
2 x AWG 16 - 12
1 x AWG 17 - 14
22.0 Lb-in.
22.0 Lb-in.
13.2 Lb-in.
14.2 Lb-in.
26.0 Lb-in.
approx.1.40 kg (incl. hub M20)
approx.0.27 kg
approx.0.38 kg
approx.1.87 kg (incl. hub M20)
approx.0.34 kg
approx.0.53 kg
approx.1.92 kg (incl. hub M20)
approx.0.38 kg
approx.0.58 kg
250 VAC
AC / 5 A
DC / 0.03 A
W
2P + N +
12h
Front view of contact
tubes of socket-outlet
or connector
10 mm
10 mm
9 mm