Heat output / COP
9.1
Heat output / coefficient of performance (COP)
1. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 55 °C flow temperature.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
2. Note that additional space is required for pipe connections, operation and maintenance.
3. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, commissioning and oper-
ation can be found in the respective sections of the installation and operating instructions. The specified values, e.g. W10 / W55, have the following meaning: Heat source
temperature 10 °C and heating water flow temperature 55 °C.
4. See CE declaration of conformity
5. The heat circulating pump and the heat pump manager must always be ready for operation.
6. The coefficients of performance are valid with the circulating pumps included in the scope of supply.
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Thermal energy meter
2.4
Installation location
2.5
Performance levels
3
Operating limits
3.1
Heating water flow
3.2
Cold waterRC (heat source)
4
Flow / sound
4.1
Heating water flow / free compression (max).
Nominal flow in accordance
Minimum heating water flow
4.2
Cold water flow rate / internal pressure differential
Nominal flow in accordance
Minimum cold water flow rate
4.3
Sound power level according to EN 12102
4.4
Sound pressure level at a distance of 1m
5
Dimensions, weight and filling quantity
2
5.1
Device dimensions
5.2
Weight of the transportable unit(s) incl. packaging
5.3
Device connections for heating
5.4
Device connections for heat source
5.5
Refrigerant / total filling weight
5.6
GWP value / CO
equivalent
2
5.7
Refrigeration circuit hermetically sealed
5.8
Lubricant / total filling quantity
5.9
Volume of heating water in device
5.10 Volume of heat transfer medium in device
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD-Type
6.2
Control voltage / fuse protection / RCD-Type
6.3
Degree of protection according to EN 60 529
6.4
Starting current with soft starter
6.5
Nominal power consumption W10 W35 / max. power consumption
Nominal current W10 W35 / cos 
6.6
EN-14
3 6
Performance level
at W10 / W55
kW / ---
at W10 / W45
kW / ---
at W10 / W35
kW / ---
°C
°C
at W10...7 / W35...28
m³/h / Pa
at W10...7 / W45...38
m³/h / Pa
at W10...7 / W55...45
m³/h / Pa
m³/h / Pa
at W10...7 / W35...28
m³/h / Pa
at W10...7 / W45...38
m³/h / Pa
at W10...7 / W55...45
m³/h / Pa
m³/h / Pa
dB(A)
1
dB(A)
H x W x L mm
kg
inches
Inches
type/kg
--- / t
type/litres
Litres
Litres
A
3
kW
A / ---
452237.66.53 · FD 9912
WI 120TU - WI 180TU
EN 14511
1
52.1 / 3.7
104.2 / 3.7
55.9 / 4.7
109.5 / 4.6
61.6 / 6.1
118.5 / 5.9
WI 180TU
Water
Universal
integrated
Integrated
Indoors
2
20 to 62 ± 2
+7 to +25
22.2 / 40000
21.2 / 43500
14.4 / 64000
14.4 / 64000
42.1 / 41500
37.2 / 32500
34.7 / 28000
34.7 / 28000
70
55
1890 x 1350 x 750
824
Rp 2½"
Rp 3"
R410A / 19.5
2088 / 41
yes
Polyolester (POE) / 14.6
26
26
3~/PE 400 V (50 Hz) / C 100A / A
1~/N/PE 230 V (50 Hz) / C 13A / A
IP 21
110
32.1 / 57.5
57.9 / 0.8