Helios EcoVent KWL EC 60 PRO Notice De Montage Et D'utilisation page 23

Masquer les pouces Voir aussi pour EcoVent KWL EC 60 PRO:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
Wall installed unit KWL EC 60 Pro / ... Pro FF
D8 = Language:
Language selection between Ger-
man, English, French or Italian.
D9 = Date and time:
Setting of the current date and time
(time zone).
D10 = Display fade-out time:
The display fade-out time can be set
between 5 - 30 seconds. If no confir-
mation at the comfort controller is
carried out for this time, the display
goes out and the control returns to
the highest menu level.
D11 = Knob light:
Location light: If the display is off, the
knob of the rotary encoder is blue
lighted. The lightness can be set bet-
ween 0 – 100 %.
Error indication: If the display is off
and an error is present, the knob of
the rotary encoder is flashing red.
The lightness can be set between 20
– 100 %.
D12 = Service menu:
Over the service menu several para-
meters can be adjusted individually.
In order to get into the password-
protected menu, enter password
5255.
E1 = Operating hours display:
The counting of the operating hours
take place as soon as one or both
fans are running.
An operating hours reset can only be
carried out in the factory.
E2 = Heat exchanger frost protec-
tion:
0 till 10° C
E3 = Min. fan speed
The minimum fan speed can be set
between level 0 and 1. If level 0 is
specified, the KWL-unit can be swit-
ched off. If level 1 is specified, level 0
cannot be activated, nor in the wee-
kly program.
E9 = Controller address
The controller address can be chan-
ged later. It should be noted that the
addresses are always only once
assigned. Maximum 4 controllers can
be connected.
E11 = Software version:
Query to the current state of the soft-
ware version of the main board and
controller
E12 = Resetting to factory setting
All parameters can be reset to fac-
tory setting. If the settings in the wee-
kly program should not be reset, this
option can be set in advance.
E13 = Motor monitoring/
fault management:
Fan speed 1:
1. With a rotational speed error in LS
1 that lasts longer than 30 seconds,
the unit switches to LS 2.
2. If the error still exists after 1 minu-
te, the unit remains in LS 2.
If the error does not exist any more,
the unit switches again to LS 1.
Fan speed 2 - 4:
In these fan speeds no automatic
switching takes place on another fan
speed.
Note: Regardless of the error eva-
luation via the speed signal, the
motor has its own error manage-
ment, which shuts down on
blocking and tries cyclically a swit-
ching on.
Error code:
E1
Status line fan "Supply air"
E2
Status line fan "Extract air"
E3
Exceeding maximum current
"Supply air"
E4
Exceeding maximum current
"Extract air"
E5
Falling below minimum current
"Supply air"
E6
Falling below minimum current
"Extract air"
E7
Terminal fault "Supply air"
E8
Terminal fault "Extract air"
E9
Supply voltage 24 V
E = 14 fan speed:
If the EC 60 unit is switched on, it
reverts to boost mode for 4 seconds,
LS 2 runs instead of LS 1.
During the boost mode "automatic
mode" is shown in the display
instead of "manual".
5
UK