Mobile Home Installation

You must use a Quadra-Fire Outside Air Kit Part #:
OAK-ACC
1.
An outside air inlet must be provided for combustion and
must remain clear of leaves, debris, ice and/or snow. It
must be unrestricted while unit is in use to prevent room air
starvation which can cause smoke spillage and an inability
to maintain a fire. Smoke spillage can also set off smoke
alarms.
2.
Unit must be secured to the mobile home structure at two
attachment points. Remove bolts from each side of insert and
use plumbers tape to secure to structure (a washer may be
required). Re-install bolts.
3.
Unit must be grounded with #8 solid copper grounding wire or
equivalent and terminated at each end with N.E.C. approved
grounding device.
The factory-built fireplace must meet (UM)84-HUD
4.
requirements for outside combustion air supply to the
fireplace fire chamber and the chimney must be listed to
UL103 HT or a listed UL-1777 full length six inch (152mm)
diameter liner must be used. It must be equipped with a spark
arrestor cap and the outside air must be installed on the
insert.
5.
Refer to pages 9-10 of this manual for clearance to
combustibles and floor protections requirements. All
clearances must be followed precisely.
6.
Use silicone to create an effective vapor barrier at the
location were the chimney or other component penetrates to
the exterior of the structure.
7.
Follow the chimney and chimney connector manufacturer's
instructions when installing the flue system for use in a mobile
home.
8.
Burn wood only. Other types of fuels may generate poisonous
gases (e.g., carbon monoxide).
9.
If unit burns poorly while an exhaust blower is on in home,
(i.e., range hood), increase combustion air.
10. Installation shall be in accordance with the Manufacturers
Home & Safety Standard (HUD) CFR 3280, Part 24.
NOTICE: Offsets from the vertical, not exceeding 45°, are
allowed per Section 905(a) of the Uniform
Mechanical Code (UMC). Offsets greater than 45°
are considered horizontal and are also allowed,
providing the horizontal run does not exceed 75%
of the vertical height of the vent. Construction,
clearance and termination must be in compliance
with the UMC Table 9C. This installation must also
comply with NFPA 211.
NOTICE: Top sections of chimney must be removable to
allow maximum clearance of 13.5 feet (411cm)
from ground level for transportation purposes.
14 Janvier, 2020
Mitre
Écran/pare-feu de solive
Figure 27.1
Fire Risk.
Asphyxiation Risk.
Do not draw outside combustion air from:
Wall, floor or ceiling cavity
Enclosed space such as an attic or garage
Close proximity to exhaust vents or chimneys
Fumes or odor may result
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED
Do NOT cut through:
Floor joist, wall, studs or ceiling trusses.
Any supporting material that would affect the structural
integrity.
Asphyxiation Risk.
NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.
FC7063-513I
VOYAGEUR Insert ACC
Chapeau pare-étincelles
Solin de toit
Carneau double paroi
WARNING
CAUTION
WARNING