Wireless remote controller
1
When TEMPORARY button is pushed for
10 seconds or more, "Pi!" sound is heard
and the operation changes to test run. After
approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor
units in test run.
TEMPORARY button
47-EN
When a test run is not
performed properly
When a test run is not performed properly, refer to
the error code and the part to be checked on
"Troubleshooting".
When a test run is executed before installing the
external duct, a protection control may be activated
and lets the unit stop and the code P12 may be
displayed. (This is not due to a malfunction but to the
current control function of the DC motor in this unit.)
When a test run executed before installing the
external duct, select "Low" for the fan speed level or
cover the air discharge.
In addition, stop the operation before replacing the
opening the service panel.
After the test run, reset the circuit breaker of the
indoor unit.
12
Maintenance
Periodic Maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. When the air
conditioner is operated for a long time, periodic maintenance (once a year) is recommended. Furthermore,
regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment,
if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work. Such maintenance can
extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage,
and even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat exchanger if
Heat exchanger
there is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there are
Fan
any waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any clogging
Drain pan
or drain water is polluted.
Maintenance List
Part
Unit
Heat exchanger
Indoor / outdoor
Fan motor
Indoor / outdoor
Filter
Indoor
Fan
Indoor
Air intake / discharge
Indoor / outdoor
grilles
Drain pan
Indoor
Ceiling panel, louvers
Indoor
Exterior
Outdoor
– 24 –
Inspection method
Check (visual / auditory)
Maintenance
Wash the heat exchanger when it is
Dust / dirt clogging, scratches
clogged.
Take appropriate measures when
Sound
abnormal sound is generated.
Wash the fi lter with water when it is
Dust / dirt, breakage
contaminated.
Replace it when it is damaged.
Replace the fan when vibration or
Vibration, balance
balance is terrible.
Dust / dirt, appearance
Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Clean the drain pan and check
Dust / dirt clogging, drain
the downward slope for smooth
contamination
drainage.
Wash them when they are
Dust / dirt, scratches
contaminated or apply repair coating.
Rust, peeling of insulator
Apply repair coating.
Peeling / lift of coat
EN
FR
ES
48-EN