Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
• Specify [01] for the Code No. in Procedure
4
• For the set data in Procedure
, select the set data
of fi lter sign term from the following table.
Set data
Filter sign term
0000
None
0001
150 H
2500 H
0002
(Factory default)
0003
5000 H
0004
10000 H
• The fi lter sign may be unavailable depending on the
remote controllers.
External static pressure
settings
To set the external static pressure, refer to the
"Fan characteristics" in 7 Duct design.
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
1
2
3
4
5
6
procedure (
).
• Specify [5d] for the Code No. in procedure
4
• For the set data of procedure
, select a set data
of the external static pressure to be set up from the
following table.
Set data
External static pressure
0000
0.4 in.WG
Factory default
0001
0.2 in.WG
0002
0.3 in.WG
0003
0.6 in.WG
0004
0.5 in.WG
0005
0.7 in.WG
0006
0.8 in.WG
43-EN
Remote controller-less setting
Change the external static pressure setting with the
DIP switch on the P.C. Board.
* Once the Set data has been changed, though it can
be freely set to 0001 or 0003, to reset it to 0000
(factory default), it need changing using remote
3
.
controller (sold separately). After setting has been
completed, restart the air conditioner.
SW501-1
OFF
ON
OFF
SW501-2
OFF
OFF
ON
Factory
Set data
0001
0003
3
.
default
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of Code No. [5d] to "0000".
All Outside Air Unit
connection setting
Other than Super Modular Multi System u series
(SMMS-e)
When only Outside Air Unit connected to Outdoor
unit, set the all Outside Air Unit connection setting at
Outside Air Unit.
Firstly, follow to the basic operation procedure
1
2
3
4
5
6
(
).
• The Code No. in procedure
4
• The Set data in procedure
Secondary, follow to the basic operation procedure
4
5
(
).
• The Code No. in procedure
4
• The Set data in procedure
Finally, follow to the basic operation procedure
4
5
6
(
).
• The Code No. in procedure
4
• The Set data in procedure
Code No.
Filter sign term
C8
AE
AF
ON
ON
0006
– 22 –
Group control
(Outside Air Unit)
• The Outside Air Unit and indoor unit for air
conditioner cannot be connected as a group control.
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to
3
"9 Electrical connection" in this Manual.
is [C8].
• Wiring between indoor units in a group is performed
is [0000].
in the following procedure.
• Connect the indoor units by connecting the remote
controller wires from the remote controller terminal
3
is [AE].
blocks (A, B) of the indoor unit connected with a
is [0016].
remote controller to the remote controller terminal
blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
3
is [AF].
is [0010].
0000
0016
0010
EN
FR
ES
44-EN