STANDARD PROGRAM
Options: ON, OFF
Default: ON
The settings can be reverted to default values in this menu. However this does not apply to the following
menus: APPLICATION, LANGUAGE, TEMP. UNIT and COUNTER. Desired changes must be done in the
menus in question. It is possible to choose only the alternative ON in this menu because when the default
settings have been changed the menu will automatically change into OFF mode.
LANGUAGE
Options: GERMAN, ENGLISH, FRENCH, FINNISH, SWEDISH, CZECH
Default: GERMAN
Various languages can be selected in this menu. The selected language will retain even if the standard
program is reverted.
TEMP. UNIT °C/°F
Options: °C, °F
Default: °C
The temperature scale can be either Celsius (°C) or Fahrenheit (°F). The selected temperature unit will retain
even if the standard program is reverted.
COUNTER
Range: 00000H00M...65535H59M
The counter calculates the time, in minutes and hours, during which the heating has been on. The counter
reading will retain even if the standard program is reverted. To reset the counter, select RESET with the
VALUE button and then press ENTER to reset.
ALARM MESSAGES
In the event of an alarm, the display starts flashing in one second intervals and the alarm relay closes (con-
nectors 5 and 6). The word ALARM appears on the top line and the reason of the alarm on the bottom line.
This alarm display alternates with the measured values so that each option is displayed 3 seconds at each
time. The heating relay opens (connectors 8 and 9) turning off the heater, unless the continuous heating
has been selected. The alarm message appears on the display still for 5 seconds after fault clearance. It is
possible to change menu options during the alarm.
Alarm
SHORT HEATER
BROKEN HEATER
SHORT TEMP
BROKEN TEMP
SHORT AIR TEMP
BROKEN AIR TEMP
SHORT MOISTURE
BROKEN MOISTURE
All manuals and user guides at all-guides.com
Fault
Heating resistor of snow and ice sensor
ECOA901 or ECOA903 short circuit
Heating resistor of snow and ice sensor
ECOA901 or ECOA903 open circuit
Temperature sensor ECOA902 or
ECOA904 short circuit
Temperature sensor ECOA902 or
ECOA904 open circuit
Air temperature sensor ECOA904 short
circuit
Air temperature sensor ECOA904 open
circuit or 82 kΩ resistor is missing
Temperature sensor in moisture sensor
of ECOA901 or ECOA903 short circuit
Temperature sensor in moisture sensor
of ECOA901 or ECOA903 open circuit
RAK41 / © Ensto 2017
Wire color
Connectors
green / brown
12 / 14
green / brown
12 / 14
yellow / brown or
18 / 19
blue / brown
yellow / brown or
18 / 19
blue / brown
brown / blue
20 / 21
brown / blue
20 / 21
yellow / brown
13 / 14
yellow / brown
13 / 14
17