The mains -input & output terminal connector G-ST18i can be found on the bottom of the
Multi Compact, see appendix 1. The shore or mains cable must be connected to the G-ST18i
connector with a three-wire cable. Use a three-wire cable with a flexible core and a cross
section of 1.5 mm² (800VA) to 2.5 mm² (1600VA).
Procedure
Proceed as follows to connect the AC cables:
The AC output cable can be connected directly to the G-ST18i male-connector. (the
connector pulls out!)
The terminal points are indicated clearly. From left to right: "N" (neutral), earth, and "L1"
(phase).
The AC input cable can be connected directly to the G-ST18I female-connector. (the
connector pulls out!)
The terminal points are indicated clearly. From left to right: "L1" (phase). earth, and "N"
(neutral).
Push the G-ST18i "input" connector into terminal connector (near to rear-side).
Push the G-ST18i "output" connector into terminal connector (near to front-side).
3.6 Optional Connections
A number of optional connections are possible:
Undo the four screws at the front of the enclosure and remove the front panel.
3.6.1 Second Battery
The Phoenix Multi Compact / MultiPlus Compact has a connection (+) for charging a starter
battery. For connection see appendix 1