Télécharger Imprimer la page

Victron energy Phoenix C 12/2000 230V Manuel page 20

Onduleur compact

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 37
8. TECHNICAL DATA
Phoenix Inverter
INVERTER
Input voltage range (V DC)
Output
Cont. output power at 25 °C (VA) (3)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero load power in search mode (W)
GENERAL
Programmable relay (4)
Protection (2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) Programmable relay which can be set for general alarm, DC undervoltage or genset start signal function
16
C 12/2000 230V
9,5 – 17 V
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
2000
1600
1450
3500
93
10
3
Operating temp. range: -20 to +50°C (fan assisted
cooling) Humidity (non condensing) : max 95%
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP 21
Bolts M8
connector
520 x 255 x 125
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
C 24/2000 230V
19 – 33 V
2000
1600
1450
3500
94
10
3
yes
a - g
6 mm², 10 AWG
12

Publicité