CAUTION
Risk of toppling
Physical injury or damage to components due to improper assembly.
• Disconnect the supply lines.
• Place the components on a suitable base (flat, solid, dry) on which they will not topple over.
• Note the maximum tilt angle of 10°.
NOTICE
• Ensure clear access to the control elements and connections.
• Install the cooling unit with a circumferential clearance of 50 cm to ensure optimum cooling air circulation.
• Prevent dust and other foreign substances from entering the system's cooling air stream.
• Protect the components from rain and direct sunlight.
• Only use the device in dry, clean and well-ventilated rooms.
6.2 Connecting the cooling unit
6.2.1 Fuse protection for the cooling unit
NOTICE
• The fuse protection differs depending on the device version:
CR1000/CR1250 with 115 V is protected by a 5A fuse.
CR1000/CR1250 with 230 V is protected by a 3A fuse.
CR1000/CR1250 with 400 V is protected by three 1A fuses.
1
CR1000 115/230 V
Fig. 8
Fuses
If the cooling unit does not work, check:
• the power supply – switch on if necessary
• the fuse (1) – replace if necessary.
BAL.0351.0 • 2020-06-10
1
1
CR1250 115/230 V
6 Putting into operation
1
1
CR1000 400 V
1
EN - 11