BURNER SET-UP CHART
NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the instal-
lation and set-up instructions supplied with the heating unit, as settings will differ from those shown in this
manual.
1
Actual firing
rate ± 5%
GPH
kg/h
1.45
4.7
1.80
5.8
2.10
6.8
2.40
7.8
2.75
8.9
2.95
9.5
NOZZLES RECCOMANDED:
Monarch R-PLP, Delavan W-B, Danfoss S-B, Steinen SS-S, Hago P.
NOTE:
A 60° degree nozzle is suggested, however, a 80° degree nozzle may be used in cases where the flame is unstable at
light-off when operated at low ambient temperatures.
DUCTED COMBUSTION AIR INTAKE APPLICATIONS
The "Ducted combustion air intake kit" (see P.N. 3002762 in the spare parts list - OPTIONAL), allows ducting of external
air directly into the burner. A 4" diameter air intake is provided in the kit.
To mount this kit on the burner, please follow the installation description given in the kit instruction sheet.
If the burner code 3726392 is used, the pre-sheared cover must be adopted (see P:N: 3020509 in the spare
parts list) to apply the 4" diameter air intake.
Use a 4" to 6" pipe adapter (not supplied in the kit) to use a 6" diameter pipe.
The settings of the burner must be according to the BURNER SETUP CHART – AIR INTAKE APPLICATIONS below.
MODEL F10 BURNER SETUP CHART with 4" diameter pipe
Actual
Nozzle
firing rate
size
GPH
1.45
1.25 x 60°/80°
1.80
1.50 x 60°/80°
2.10
1.75 x 60°/80°
2.40
2.00 x 60°/80°
2.75
2.25 x 60°/80°
MODEL F10 BURNER SETUP CHART with 6" diameter pipe
Actual
Nozzle
firing rate
size
GPH
1.45
1.25 x 60°/80°
1.80
1.50 x 60°/80°
2.10
1.75 x 60°/80°
2.40
2.00 x 60°/80°
2.75
2.25 x 60°/80°
2.89
2.50 x 60°/80°
2902451
2
Nozzle
size
pressure
GPH
PSI
1.25 x 60°
145
1.50 x 60°
145
1.75 x 60°
145
2.00 x 60°
145
2.25 x 60°
150
2.50 x 60°
140
Pump
Head
pressure
setting
PSI
145
1.5
145
2.0
145
2.5
145
3.5
150
5.0
Pump
Head
pressure
setting
PSI
145
1.5
145
2.0
145
2.5
145
3.5
150
4.5
145
5.0
3
Pump
Turbulator
setting
bar
10
10
10
10
10.4
9.8
20 Ft.
50 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.3
2.4
2.9
3.0
3.7
3.8
4.4
4.5
5.5
6.0
20 Ft.
50 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.3
2.4
2.8
2.8
3.5
3.5
4.2
4.2
5.2
5.2
6.0
6.0
12
4
Air damper
setting
1.5
2.7
2.0
2.8
2.5
3.1
3.5
3.4
4.0
4.2
4.5
4.2
80 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.5
3.0
3.8
4.5
6.4
80 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.4
2.9
3.6
4.3
5.5
7.0
GB
5
100 Ft.
2.5
3.0
3.8
4.5
6.5
100 Ft.
2.5
2.9
3.7
4.4
6.5
8.0

Publicité