Champ LED Floodlight
NFMVA20L/25L LED Fixtures
Installation & Maintenance Information
APPLICATION
LED floodlight construction is designed for use indoors and outdoors in marine and wet
locations, where moisture, dirt, corrosion, vibration and rough usage may be present.
NFMV:
IECEx:
IEC, ATEX:
IECEx UL 15.0029X
DEMKO 15 ATEX 1377X
DEMKO 15 ATEX 1383
Ex ec IIC T4 Gc Tamb -40°C to +55°C
Ex tb IIIC T81C Db Tamb -40°C to +40°C
II 3 G Ex ec IIC T4 Gc Tamb -40°C to +55°C
II 2 D Ex tb IIIC T81C Db IP66 Tamb -40°C to +40°C
Refer to the floodlight nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature (T-number).
To avoid the risk of fire, explosion or electric shock, this product should be
installed, inspected and maintained by a qualified electrician only, in accordance
with all applicable electrical codes.
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Floodlight must be supplied by a wiring system suitable per local code with
an equipment grounding conductor.
To avoid burning hands:
Make sure LEDs and drivers are cool to touch when performing
maintenance.
INSTALLATION
Mounting
Yoke Mount - Wall Mount Using Floodlight Yoke Only
1.
Using floodlight yoke as a template, mark and drill desired location on mounting
surface.
2.
Secure floodlight yoke to surface using ½" bolts or lag screws (not provided).
WIRING
Wiring the Floodlight
1.
Open back cover/heat sink by loosening nine (9) #10-24 x 0.75" stainless steel
cover screws using a 5/16" nut socket or flat head screwdriver (see Figure 1).
The heat sink cover should be removed by pulling back on one corner of the top
The heat sink cover should be removed by pulling back on one corner of the top
most edge to prevent damage to gasket.
most edge to prevent damage to gasket.
NOTE: To avoid pinching hazard between heat sink cover and driver housing, ensure
that floodlight is oriented in vertical position before, and during, wiring procedure.
2.
All components in the fixture are pre-wired so only line in, neutral and ground
need to be connected in the fixture using the supplied Wago connectors, using
methods that comply with all applicable codes. See Figure 2 for wiring diagram.
Wire range from AWG 18-14 (0.75 - 2.5mm²) for neutral, and line (strip
length 0.43" [10.9mm]), and AWG 16-14 (1.5 - 2.5mm²) for ground
connections (strip length 0.43" [10.9mm]).
Entries to driver housing shall be sealed, using HTL or STL, with
devices rated a minimum of IP66.
Standard openings are M20, M25 or 3/4" NPT.
Optional openings are M20 (20mm) and/or M25 (25mm).
Secure all electrical connections and wiring entry glands.
Ensure that the following lengths for field wiring, internal to the driver
housing compartment, are followed:
– 4.5" ± 0.25" (114 ± 6mm) for ground wire
– 2.5" ± 0.25" (64 ± 6mm) for neutral wire
– 2" ± 0.25" (51 ± 6mm) for line in wire
IF 1848 • 05/22
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING
WARNING
(see Figure 1).
LINE TERMINAL
NEUTRAL TERMINAL
GROUND TERMINAL
Copyright
IEC STANDARDS:
IEC 60079-0:2011+ Corr.1(2012-01) + Corr. 2 (2013-12) + I-SH 01 (2013-11) + I-SH
02 (2014-10) / EN 60079-0:2012 + A11:2013
IEC 60079-7:2017/ EN 60079-7:2015
IEC 60079-31:2013/ EN 60079-31:2014
IEC 60598-1:2008/EN60598-1:2008
IEC 60598-2:2008/EN60598-2:2008
IP66
LED floodlights are supplied for use with a choice of voltages:
• 100-277 VAC, 50/60 Hz and 127-300 VDC
• 347-440 VAC, 50/60 Hz
This product contains a light source of energy efficiency class D or E.
To avoid explosion:
Make sure the supply voltage is the same as the rated floodlight voltage.
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
Use only replacement parts from Eaton's Crouse-Hinds Division.
Use proper supply wiring as specified on the floodlight nameplate.
All surfaces must be clean.
LED compartment non-serviceable. Do not open.
Before opening wiring compartment, electrical power to the floodlight
must be turned off and area must be free from hazardous atmosphere.
Keep tightly closed when in operation.
To minimize the risk from electrostatic discharge, when cleaning, wipe the
lens with a clean, damp cloth.
DO NOT PLACE
ADDITIONAL WEIGHT
ON THE BACK COVER/
HEAT SINK
2022, Eaton's Crouse-Hinds Division
®
Directive EU 2022/2015
WARNING
Cover/heat sink
Figure 1
IF 1848
COVER SCREWS
Page 1
Table des Matières
loading

Sommaire des Matières pour Eaton NFMVA20L

  • Page 4 Ne pas faire fonctionner à des températures ambiantes supérieures à celles indiquées AVERTISSEMENT sur la plaque signalétique du réflecteur. • Utiliser uniquement des pièces de rechange d’Eaton’s Crouse-Hinds Division. Pour éviter toute décharge électrique : • Utiliser des câbles d’alimentation appropriés comme spécifié sur la plaque signalétique •...
  • Page 5: Schéma De Câblage

    Crouse-Hinds (adresse : 1201 Wolf Street, Syracuse, New York 13208; téléphone : 1-866-764-5454). Pour éviter l’allumage des atmosphères dangereuses ou la surchauffe du réflecteur : Ne pas placer le réflecteur au-delà des limites de la plage cible. IF 1848 • 05/22 © Eaton’s Crouse-Hinds Division, 2022 Page 2...
  • Page 6 Toutes les déclarations et les informations techniques contenues dans le présent document sont basées sur des informations et des essais que nous croyons fiables. Leur exactitude ou leur exhaustivité ne sont pas garanties. Conformément aux conditions de vente d’Eaton’s Crouse-Hinds Division, et étant donné que les conditions d’utilisation sont hors de notre contrôle, l’acheteur doit déterminer si le produit convient à...