01

General information

Hoesch products set the benchmark for quality, comfort and design. To assure optimal function and a long life cycle of your product
please comply with the following instructions. Each delivery is strictly controlled before leaving the factory. Check the completeness
of the delivery before starting installation. Products represented here are subject to technical and visual modifi cations! All dimensions
data is in mm. All connection measures are internal measurements! We are not liable for defects resulting from non-conventional usage,
improper transport or faulty intermediate storage. Our respectively valid warranty conditions are in force.
During mounting protect the surface of shower tray with cover!
Do not put glass panes on rims or corners!
Caution!
Check the delivery for transport damage! Later claims will not be accepted!
The choice of raw plug and screws depends upon the wall's material!
Water connections
At installation to potable water supply, service technician or user must connect fi rst a safety device according to local
regulations. It should be noted that a backfl ow protection device willingly (EN61770) (VDE 0700 Part 600) in water connection
must be provided by the user.
Penetrations through walls must be sealed with permanently elastic joint sealant. The installation must be rinsed acc. to
DIN1988.
The customer must provide a dirt pan in the interior installation.
We point out that water-softening equipment should be installed to soften water supplied to the steam generator!
Hot water supply DN 15/20 supply Rp ½", recommended fl ow pressure 200-500 kPa, 60-70ºC.
Attention: thermal disinfection (short time temperature increase up to 70ºC) should be ensured!
Cold water connection DN 15/20 supply Rp ½", recommended fl ow pressure 200-500 kPa.
A ball shut-off valve R ½" shall be provided for both connections.
Wall outfl ow DN 50/40 for steam generator drainage - see point 07.
Wall-concealed siphon included in connection set (Art.-no 27775)
Please note:
During the pipe installation a siphon for wall mounting (item no. 27775) is required, to ensure an unproblematic
installation of the SensePerience panel. A siphon for wall mounting is required for the draining of the steam
generator!
Electrical installation
A separate feed cable of 3x2.5mm² ( 2m long out of the wall) and a ground cable 1x4mm² should be provided for electrical
connection (230V, 50/60 Hz, 16A - 3,3kW / 20A - 4,0kW) according to point 07.
The device must be protected by a separate FI-switch / RCD (30mA), which disconnects all poles of the system with a contact
opening at least 3 mm wide. We strongly recommend to connect the unit to power supply system via all -poles power cut-off
switch (16A - 3,3kW / 20A - 4,0kW, min. 3mm opening width, please pay attention to protection areas).
The device must be connected to the mains electricity supply in accordance with the building regulations using all-pole
disconnecting mains switch.
The device should be connected to electricity only via a fi xed feed cable according to local regulations. Installation and repair
should be performed only by authorized service.
Note:
All electrical work must be performed by a qualifi ed electrician in accordance with DIN/EN specifi cations (DIN VDE
0100-701, etc.), national regulations and local EVU regulations!
Note:
Please note the following: once our product has been installed in your home, it becomes a part of your drinking water system.
This means that the widely accepted rules regarding hygiene apply to your use of our product too. In particular, it is assumed
that water will always be replaced within a maximum of 72 hours to eliminate the risk of it stagnating and any potential
consequences this may have.
In light of this, please note the following basic principles: If you...
are away for between several hours and two days, let the stagnant water drain off
are away for between two days and four weeks, shut the valve on your water meter or, if you live in an apartment, shut the
valve on your fl oor and open it again when you return. Leave the water to run for around fi ve minutes afterwards.
are away for more than four weeks shut the water valves in your home/on your fl oor, rinse the drinking water system out when
you return and then open the valve again afterwards
are away for more than six months, close the main isolating valve before you leave home, empty the pipes and disconnect the
feed line. When you return, open the main isolating valve again and rinse out the drinking water system.
In addition to these measures, you should also replace the water at regular intervals – at least once a month – and leave it to
run for several minutes.